| 2017-09-07 09:20:25 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060359 |
| | 9/7/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | MANY OF THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND |
| | STILL EXIST. I HAVE REPRINTED THOSE COMMENTS BELOW- |
| | PLEASE COMPLY. |
| | |
| | 2) M1: KITCHEN EXHAUST AT A RATE OF .070 PER SF. IS |
| | REQUIRED PER TABLE 403.3, AND RECIRCULATION OF AIR FROM |
| | THAT SPACE IS PROHIBITED PER FOOTNOTE B. THE MECHANICAL |
| | PLAN IN ITS CURRENT DESIGN IS NOT IN COMPLIANCE AS IT |
| | CLEARLY SHOWS RTU-1 & 2 IS RECIRCULATING AIR FROM THE |
| | KITCHEN INTO THE DINING ROOM. |
| | |
| | 3) M1: PROVIDE IN THE AC EQUIPMENT SCHEDULES THE AMOUNT |
| | OF O/A BEING SUPPLIED BY EACH UNIT. |
| | |
| | 4) M1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN |
| | AIR SYSTEM OF RTU-1 PER SECTION 606.2.1. THIS |
| | REQUIREMENT IS BASED ON THE FACT THAT A TYPICAL 5-TON |
| | SYSTEM CAN PRODUCE SUPPLY AIR IN EXCESS OF 2000 CFMS. |
| | PROVIDE A SYMBOL ON THE PLAN TO SHOW THE LOCATION OF |
| | THE DETECTOR AND INDICATE HOW IT WILL BE SUPERVISED PER |
| | SECTION 606.4.1. |
| | |
| | 5) PROVIDE A COMPLETE KITCHEN EQUIPMENT PLAN THAT |
| | INDICATES MAKES AND MODELS OF ALL NEW AND EXISTING |
| | EQUIPMENT. SUBMIT SPEC SHEETS FOR ALL NEW EQUIPMENT |
| | INCLUDING THE NEW FRYER. PLEASE NOTE THAT INSTALLATION |
| | OF GAS-FIRE APPLIANCES WILL REQUIRE SUBMITTAL OF A GAS |
| | PIPING ISOMNETRIC DRAWING, COMBUSTION AIR CALULATIONS, |
| | AND SUBMITTALS OF SEPARATE PERMITS AND PLANS FOR A |
| | GREASE |
| | |
| | EXHAUST HOOD AND FIRE SUPPRESSION SYSTEM. |
| | |
| | 6) PROVIDE COMBUSTION AIR CALULATIONS. |
| | |
| | 7) PROVIDE AN AIR BALANCE CALCULATION. |
| | |
| | 8) INDICATE THE SIZES OF THE MAIN TRUNK LINES FROM THE |
| | RTU'S. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |