| Plan Review Notes For Permit 17060359 |
| Permit Number |
17060359 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-17 14:32:11 | GAS PLAN REVIEW DENIED, | | | A GAS PLAN HAS BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. | | | A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. | | | A SEPARATE GAS PERMIT WILL BE REQUIRED FOR A CONTRACTOR | | | TO PERFORM THE RELATED WORK. WPB AMENDMENTS TO FBC SEC. | | | 107.2.1. | | | | | | 1. 2ND REQUEST, WITH THE GAS WATER HEATER NOW BEING IN | | | A CLOSET PLEASE PROVIDE SPECIFICATIONS FOR THE WATER | | | HEATER AND THE REQUIRED MAKE UP AIR FOR THE ROOM TO | | | COMPLY WITH 2014 FBC FG SEC. 304. FBC 102.7.1 | | | 2. 2ND REQUEST, PLEASE PROVIDE THE SIZING TABLE USED IN | | | SIZING SYSTEM FROM 2014 FBC FG 402. | | | 3. 2ND REQUEST, THE COMBUSTION AIR CALCULATIONS SHOW A | | | TOTAL BTU LOAD OF 166,000 THE PLAN SHOWS 589,000 PLEASE | | | PROVIDE AN ACCURATE COMBUSTION AIR CALCULATION. PER | | | 2014 FBC FG 304. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | | | | |
|