2018-03-17 14:32:11GAS PLAN REVIEW DENIED,
 A GAS PLAN HAS BEEN INCLUDED IN THIS SUBMITTAL PACKAGE.
 A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT THIS TIME.
 A SEPARATE GAS PERMIT WILL BE REQUIRED FOR A CONTRACTOR
 TO PERFORM THE RELATED WORK. WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 1. 2ND REQUEST, WITH THE GAS WATER HEATER NOW BEING IN
 A CLOSET PLEASE PROVIDE SPECIFICATIONS FOR THE WATER
 HEATER AND THE REQUIRED MAKE UP AIR FOR THE ROOM TO
 COMPLY WITH 2014 FBC FG SEC. 304. FBC 102.7.1
 2. 2ND REQUEST, PLEASE PROVIDE THE SIZING TABLE USED IN
 SIZING SYSTEM FROM 2014 FBC FG 402.
 3. 2ND REQUEST, THE COMBUSTION AIR CALCULATIONS SHOW A
 TOTAL BTU LOAD OF 166,000 THE PLAN SHOWS 589,000 PLEASE
 PROVIDE AN ACCURATE COMBUSTION AIR CALCULATION. PER
 2014 FBC FG 304.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  