| 2017-09-14 11:05:44 | PERMIT # 17060359 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | 2ND REVIEW |
| | |
| | 2ND REVIEW - SAME COMMENT |
| | 1) SHEET A4: THE DINING ROOM SEATING LAYOUT APPEARS |
| | OVER CONCENTRATED. PLEASE CONFIRM SEATING LAYOUT |
| | COMPLIES WITH NFPA 101: CHAPTER 12 - NEW ASSEMBLY |
| | OCCUPANCIES; SPECIFICALLY SECTIONS 12.2.5.7 AND |
| | 12.2.5.8, AISLE ACCESSWAYS AND AISLES SERVING SEATING |
| | AT TABLES. |
| | DOES NOT APPEAR TO HAVE BEEN ADDRESSED FROM THE 1ST |
| | REVIEW, NO NOTES OR NARRATIVE PROVIDED WITH |
| | RESUBMISSION. |
| | |
| | 2ND REVIEW - SAME COMMENT |
| | 2) SHEET A4; TWO MEANS OF EGRESS ARE REQUIRED FOR |
| | ASSEMBLY OCCUPANCIES. PER NFPA 101, SECTION 7.5.2.1, |
| | ACCESS TO AN EXIT SHALL NOT BE THROUGH KITCHENS, |
| | STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND |
| | 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR |
| | SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO LOCKING. |
| | DOES NOT APPEAR TO HAVE BEEN ADDRESSED FROM THE 1ST |
| | REVIEW, NO NOTES OR NARRATIVE PROVIDED WITH |
| | RESUBMISSION. |
| | |
| | 3) NEW COMMENT: THE REMOTENESS BETWEEN THE REQUIRED |
| | EXITS SHALL COMPLY WITH THE FOLLOWING: |
| | 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 7.5.1.3.1 THROUGH 7.5.1.3.7. |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION |
| | THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| | SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| | OTHER |
| | EMERGENCY CONDITION. |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A |
| | DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE |
| | LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT |
| | LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT |
| | ACCESSES, |
| | OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN |
| | 7.5.1.3.3 THROUGH 7.5.1.3.5. |
| | 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION |
| | DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2, |
| | SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE |
| | MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE |
| | SERVED. |
| | |
| | 4) IF FIRE SPRINKLER AND/OR FIRE ALARM MODIFICATIONS |
| | ARE REQUIRED SEPARATE PLANS AND PERMITS WILL BE |
| | REQUIRED FOR THAT WORK. |
| | |
| | 2ND REVIEW - SAME COMMENT |
| | 5) PLEASE REVIEW AND RESPOND TO BUILDING DEPT. |
| | COMMENTS. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 644-7326 |
| | |