2017-09-14 11:05:44PERMIT # 17060359
 REVIEW COMMENTS - FIRE DEPARTMENT
 2ND REVIEW
  
 2ND REVIEW - SAME COMMENT
 1) SHEET A4: THE DINING ROOM SEATING LAYOUT APPEARS
 OVER CONCENTRATED. PLEASE CONFIRM SEATING LAYOUT
 COMPLIES WITH NFPA 101: CHAPTER 12 - NEW ASSEMBLY
 OCCUPANCIES; SPECIFICALLY SECTIONS 12.2.5.7 AND
 12.2.5.8, AISLE ACCESSWAYS AND AISLES SERVING SEATING
 AT TABLES.
 DOES NOT APPEAR TO HAVE BEEN ADDRESSED FROM THE 1ST
 REVIEW, NO NOTES OR NARRATIVE PROVIDED WITH
 RESUBMISSION.
  
 2ND REVIEW - SAME COMMENT
 2) SHEET A4; TWO MEANS OF EGRESS ARE REQUIRED FOR
 ASSEMBLY OCCUPANCIES. PER NFPA 101, SECTION 7.5.2.1,
 ACCESS TO AN EXIT SHALL NOT BE THROUGH KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR
 SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO LOCKING.
 DOES NOT APPEAR TO HAVE BEEN ADDRESSED FROM THE 1ST
 REVIEW, NO NOTES OR NARRATIVE PROVIDED WITH
 RESUBMISSION.
  
 3) NEW COMMENT: THE REMOTENESS BETWEEN THE REQUIRED
 EXITS SHALL COMPLY WITH THE FOLLOWING:
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION
 THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER
 EMERGENCY CONDITION.
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES,
 OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN
 7.5.1.3.3 THROUGH 7.5.1.3.5.
 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION
 DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2,
 SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE
 MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE
 SERVED.
  
 4) IF FIRE SPRINKLER AND/OR FIRE ALARM MODIFICATIONS
 ARE REQUIRED SEPARATE PLANS AND PERMITS WILL BE
 REQUIRED FOR THAT WORK.
  
 2ND REVIEW - SAME COMMENT
 5) PLEASE REVIEW AND RESPOND TO BUILDING DEPT.
 COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  