| 2017-06-13 14:19:51 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. DUE TO THE ALTERATION OF THE LAYOUT OF THE BATHROOM |
| | IT NO LONGER MEETS ACCESSIBILITY REQUIREMENTS THE WIDTH |
| | OF THE BATHROOM OF 70" DOES NOT ALLOW FOR THE 60" |
| | CLEARANCE FOR THE TOILET THE LAVATORY CAN NOT ENCROACH |
| | ON THIS CLEAR FLOOR SPACE . PER FBC ACC 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | 604.3.2 OVERLAP. |
| | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 2. AN ALTERATION THAT DECREASES OR HAS THE EFFECT OF |
| | DECREASING THE ACCESSIBILITY OF A BUILDING OR FACILITY |
| | BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME |
| | OF THE ALTERATION IS PROHIBITED. PER FBC ACC 202.3.1 |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 603-604-606 PER |
| | FBC ACC 213 |
| | |
| | 4. SHT P-1 APPEARS TO BE FROM A DIFFERENT PROJECT THE |
| | LAYOUT IS COMPLETELY DIFFERENT AND THE JOB NAME AND |
| | ADDRESS DO NOT MATCH THE REST OF THE PLAN PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |