2017-06-12 09:05:48CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHEET E1, ELECTRICAL NOTES > MATERIALS. THERE ARE
 SEVERAL ITEMS LISTED THAT DO NOT APPLY TO THE
 ELECTRICAL INSTALLATION. PLEASE REMOVE INFORMATION THAT
 IS NOT RELEVANT OR USED FOR THE ELECTRICAL PLAN. FBC
 107.2.1
 2. PROVIDE RISER DIAGRAM. THE ELECTRICAL PLAN SHOWS TWO
 200 AMP PANELS (A & B), BUT THERE IS ONLY ONE AREA
 INDICATED FOR A 200 AMP SERVICE ON THE EXTERIOR OF THE
 BUILDING. PLEASE CLARIFY AND/OR CORRECT. NEC 215.5, FBC
 107.2.1
 3. PANEL A, CIRCUITS 2,4 AND 6,8 SHOW A #12 WIRE ON A
 30 AMP BREAKER. PROVIDE CORRECTION. NEC 240.4;
 310.15(B)(16)
 4. PANEL A, CIRCUIT 10 SHOWS A #12 WIRE ON A 25 AMP
 BREAKER. PROVIDE CORRECTION. NEC 240.4; 310.15(B)(16)
 5. PROVIDE DETAIL FOR METHOD OF FAN CONTROL SPECIFIED
 IN ELECTRICAL NOTE>ELECTRICAL CONTRACTOR>D. FBC
 107.2.1; FBC MECH. 503.1
 6. SHOW ON PLAN GFCI PROTECTION FOR ALL OUTLETS IN
 KITCHEN AND BAR AREAS. NEC 210.8(B)(2)
 7. IDENTIFY RTU LOCATIONS(WITH UNIQUE IDENTIFICATION)
 AND THE CIRCUITS THAT FEED THEM. CURRENTLY, THE
 CIRCUITS ARE MARKED AS FED FROM PANEL A, WHICH DOES NOT
 CORRESPOND WITH THE PANEL SCHEDULE. GFCI CONVENIENCE
 OUTLET CIRCUITS ARE NOT IDENTIFIED. FBC 107.2.1, NEC
 210.63, 210.8
 8. SHOW ON PLAN THE LOCATION OF REQUIRED SHOW WINDOW
 OUTLETS AND SIGN CIRCUIT. PROVIDE DETAIL OF AUTOMATIC
 CONTROL OF THESE ITEMS. FBC 107.2.1; FBC C405.2.2 AND
 C405.2.4
 9. ON SHEET E1 THERE IS A J-BOX WITH CIRCUITS B-17,19
 LOCATED IN THE KITCHEN. PROVIDE CLARIFICATION. IS THIS
 A POWER CIRCUIT FOR SOMETHING, OR A LIGHTING CIRCUIT AS
 THE PANEL SCHEDULE INDICATES? FBC 107.2.1
 10. PROVIDE DETAILS OF LIGHTING CONTROL FOR DINING ROOM
 AND BAR AREA. FBC C405.2.2.1
 11. PROVIDE DETAIL SHOWING THAT THE LIGHTING ALLOWANCE
 PER THE ENERGY CONSERVATION CODE IS MET. YOU CURRENTLY
 HAVE A NOTE THAT STATES THE SYSTEM IS DESIGNED PER 2014
 ENERGY CONSERVATION SECTION 505, WHICH DOES NOT EXIST.
 FBC C405.5.2
 12. PROVIDE DETAIL OF SHUT DOWN FOR ANY ELECTRICAL
 EQUIPMENT UNDER THE HOOD. FBC MECHANICAL 503.1; NFPA 96
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER