Plan Review Notes
Plan Review Notes For Permit 17060359
Permit Number 17060359
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-13 12:03:39****HOLDS HAVE BEEN PLACED ON UNITS 26, 27, 28 - NO
 PERMITS OR BUSINESS TAX TO BE ISSUED UNTIL THE EXITING
 ISSUE HAS BEEN RESOLVED - PERMIT AND BUSINESS TAX
 RECEIPT APPLICATIONS MAY BE SUBMITTED BUT WILL NOT BE
 ISSUED UNTIL THE EXITING ISSUE IS RESOLVED, SEE COMMENT
 #3****
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. P1 HAS INCORRECT JOB INFORMATION IN THE TITLE BLOCK,
 REVISE.
  
 2. THIS PROPERTY HAS A NUMBER OF EXPIRED PERMITS,
 PLEASE CONTACT [email protected] TO RESOLVE. PLEASE
 ADVISE AS TO ACTION PROPOSED TO GET THE EXPIRED PERMITS
 CLOSED. PERMITS AND APPLICATIONS EXPIRE AFTER 180 DAYS
 OF INACTIVITY; NOTE THAT SOME PERMITS OR PERMIT
 APPLICATIONS MAY BE EXPIRED EVEN IF OUR SYSTEM SHOW
 THEM IN "OPEN" STATUS RATHER THAN "EXPIRED".
  
 3. THIS RESTAURANT AREA PREVIOUSLY OCCUPIED UNITS 26,
 27, AND 28 (WALL SEPARATING UNITS 27 AND 28 REMOVED
 WITH PERMIT 12060109, COMBINED UNITS 26-28 RENOVATED
 INTO ONE RESTAURANT). UNIT 28 THEN PROVIDED THE
 REQUIRED SECOND EXIT.
  
 PERMIT #17010091, PLAN PREPARED BY MARK S. BEATTY
 AR92184 WAS SUBMITTED AND ISSUED TO SEPARATE UNIT 28
 FROM UNITS 26/27. THE PLAN DID NOT SHOW EXISTING
 OCCUPANCY OR ROOM DESIGNATIONS. THIS PERMIT CREATED A
 LIFE SAFETY ISSUE WHICH MUST BE CORRECTED BEFORE UNITS
 26/27 CAN BE OCCUPIED.
  
 THE DINING AREA, WITH AN OCCUPANT LOAD OF 151, HAS BEEN
 DESIGNED TO HAVE ONLY ONE COMPLIANT EXIT, TWO REQUIRED.
  
 PAPA RECORDS SHOW YEAR BUILT AS 1987. STANDARD BUILDING
 CODE 1982 (ALSO SBC1985, SBC1988) REQUIREMENTS WERE
 SIMILAR TO CURRENT CODE - TWO EXITS REQUIRED, EXITING
 THROUGH KITCHENS PROHIBITED.
  
 IT IS NOT CLEAR WHY PERMIT 17010091 DID NOT DISCLOSE
 THAT INSTALLATION OF A WALL CREATED AN EXITING ISSUE,
 AND WHY PERMIT APPLICATION 17060359 DID NOT CORRECT THE
 LIFE SAFETY VIOLATION.
  
 5. THE SEATING PLAN ON A4 DOES NOT INCLUDE AN
 ACCESSIBLE ROUTE, FBC A CHAPTER 4, COMPLIANCE WITH
 ACCESSIBLE SEATING REQUIREMENTS NOT SHOWN. ALTHOUGH
 THIS REVIEW DOES NOT COVER MOVEABLE SEATS, A PLAN WHICH
 OBVIOUSLY DOES NOT COMPLY WITH FEDERAL LAW CANNOT BE
 STAMPED AS APPROVED.
  
 6. PROVIDE A DETAIL FOR THE BAR SHOWING COMPLIANCE WITH
 FBC A 226, 902.
  
 7. EVIDENCE THAT THE ADVANCED FLORIDA BUILDING CODE
 COURSE WAS TAKEN IS REQUIRED TO BE SENT TO FBPE SO THAT
 THE DBPR WEBSITE CAN BE UPDATED (JAMES BIAGI,PE),
 PLEASE ADDRESS PRIOR TO RESUBMITTAL, FS471.0195. THIS
 COMMENT DOES NOT PREVENT THIS PERMIT FROM BEING ISSUED.
  
 8. SHEET A1 SHOWS THIS UNIT AS IN THE "NORTH WEST
 WING"' NOT CLEAR WHAT THIS MEANS. REVISE THE PLANS AND
 APPLICATION TO INCLUDE UNIT NUMBERS. BASED ON THE
 PHOTOGRAPH, I WAS ABLE TO DETERMINE THAT THIS IS LIKELY
 THE UNITS REFERENCED IN COMMENT #3, WHICH ARE IN THE
 CENTER OF THE STRIP MALL. IT HAS AN EAST/WEST
 ORIENTATION, NOT CLEAR HOW THIS IS IN A "NORTH WEST
 WING."
  
 9. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.