| 2017-07-25 12:25:00 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | PREVIOUS COMMENT HAS NOT COMPLIED 2ND REQUEST 3. SUBMIT |
| | CALCULATIONS FOR COMBUSTION AIR PER THE FBC-2014 FUEL |
| | GAS CODE SEC. 304. |
| | |
| | THE RESPONSE TO THIS COMMENT IS INCORRECT THE SECTION |
| | OF THE FBC FG 505.2 DOES NOT EXIST AND SEC 505 DEALS |
| | WITH DIRECT-VENT AND INTEGRAL VENT APPLIANCES AND |
| | MECHANICAL VENTING SYSTEMS AND EXHAUST HOOD VENTING |
| | |
| | COMBUSTION AIR SHALL COMPLY WITH FBC FG 304.1 GENERAL. |
| | AIR FOR COMBUSTION, VENTILATION AND DILUTION OF FLUE |
| | GASES FOR APPLIANCES INSTALLED IN BUILDINGS SHALL BE |
| | PROVIDED BY APPLICATION OF ONE OF THE METHODS |
| | PRESCRIBED IN SECTIONS 304.5 THROUGH 304.9. WHERE THE |
| | REQUIREMENTS OF SECTION 304.5 ARE NOT MET, OUTDOOR AIR |
| | SHALL BE INTRODUCED IN ACCORDANCE WITH ONE OF THE |
| | METHODS PRESCRIBED IN SECTIONS 304.6 THROUGH 304.9. |
| | DIRECT-VENT APPLIANCES, GAS APPLIANCES OF OTHER THAN |
| | NATURAL DRAFT DESIGN AND VENTED GAS APPLIANCES OTHER |
| | THAN CATEGORY I SHALL BE PROVIDED WITH COMBUSTION, |
| | VENTILATION AND DILUTION AIR IN ACCORDANCE WITH THE |
| | APPLIANCE MANUFACTURER?S INSTRUCTIONS. |
| | |
| | THE ONLY EXCEPTION FOR COMBUSTION AIR IS FOR CLOTHES |
| | DRYERS |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |