| 2017-06-14 16:52:56 | 1ST REVIEW: FBC 2014 5TH ED. |
| | 1ST REVIEW FBC 2014 EXISTING BUILDING |
| | |
| | PLEASE SUPPLY MORE DETAIL AS TO THE SQUARE FOOTAGE OF |
| | THE INSTALLATION EITHER BY FLOOR PLAN OR A PROPOSAL TO |
| | DEMONSTRATE THE SIZE AND VALUE OF THE INSSTALLATION. |
| | NOTE THE PERMIT FEE IS BASED UPON HE FULL MARKET VALUE |
| | OF THE FLOOR SYSTEM INCLUDING THE TILE. IT APPEARS THIS |
| | IS FOR A BEDROOM. MOST BEDROOMS ARE A MINIMUM OF 100 |
| | SQUARE FEET, SO AT A $10.00/SF RATE, YOUR VALUE APPEARS |
| | FINE BUT NONETHELESS, PLEASE PROVIDE THE INFORMATION. |
| | |
| | TWO COPIES OF TEST REPORTS FOR THE UNDERLAYMENT IS |
| | REQUIRED TO BE SUBMITTED TO DEMONSTRATE COMPLIANCE WITH |
| | THE SECTIONS BELOW IN THE INSTALLED CONDITION. I WILL |
| | EMAIL TO YOU AN EXAMPLE OF A TYPICAL SUBMITTAL. |
| | |
| | FBC 603.1 FLAME SPREAD |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | |
| | STEVEN KENNEDY, CBO |