Plan Review Notes
Plan Review Notes For Permit 17060349
Permit Number 17060349
Review Stop G
Sequence Number 1
Notes
Date Text
2017-06-13 03:07:121) SHT. P1 - THERE ARE SECTIONS OF PRINTING ON THE GAS
 RISER DRAWING THAT ARE ILLEGIBLE. SUBMIT A CLEAR AND
 LEGIBLE SHEET THAT REFLECTS THE SCOPE OF WORK BEING
 DONE. WPB AMEND. TO FBC SEC. 107.2.1.
 2) DOES THIS NEW GAS METER SERVE ONLY THE TANKLESS
 WATER HEATER AND THE FUTURE POOL HEATER OR IS THE
 GENERATOR ALSO INCLUDED ON THIS SERVICE. THE PLAN SHOWS
 THE GENERATOR CONNECTED TO AN EXISTING GAS METER BUT
 THE PLANS DO NOT SHOW IF THE EXISTING GAS METER IS
 REMAINING OR BEING REPLACED BY THE NEW. IF THE
 GENERATOR IS SERVED BY THE NEW METER THE BTU LOAD OF
 THE GENERATOR MUST BE ADDED TO THE TOTAL LOAD ON THE
 SYSTEM. CLARIFY ON THE PLANS.
 3) SHOW THE BTU LOAD FOR THE FUTURE POOL HEATER. THIS
 VALUE MUST BE INCLUDED IN THE SIZING OF THE SYSTEM.
 FBC-FUEL GAS SEC.402.2.
 4) SUBMIT TWO COPIES OF THE TABLE FOR INSTALLATION
 CLEARANCES FROM THE RINNAI INSTALLATION MANUAL. THE
 MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12
 INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE
 LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN
 AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM
 EACH. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW