Notes
Date Text
2017-06-12 15:47:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO REFERENCES OF COMPLIANCE WITH ANY FIRE
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 ON THE SUBMITTAL.
  
  
  
 2) ALL SUBMITTED SHEETS - FLOORING AND SOUND BARRIERS
 ARE BEING PROPOSED FOR THIS PROJECT. THERE ARE NO
 PRODUCT SUBMITTALS.
  
 31.3.3.3 INTERIOR FLOOR FINISH. IN BUILDINGS UTILIZING
 OPTION 1 OR OPTION 2, NEWLY INSTALLED INTERIOR FLOOR
 FINISH IN EXITS AND EXIT ACCESS CORRIDORS SHALL BE NOT
 LESS THAN CLASS II IN ACCORDANCE WITH 10.2.7.
  
 YOUR BUILDING DOES NOT HAVE A SUPPRESSION SYSTEM BUT
 DOES HAVE A FIRE ALARM, USING (2) OPTION 2, BUILDINGS
 PROVIDED WITH A COMPLETE APPROVED AUTOMATIC FIRE
 DETECTION AND NOTIFICATION SYSTEM IN ACCORDANCE WITH
 31.3.4.4
  
 10.2.7 INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1 CARPET AND CARPETLIKE INTERIOR FLOOR FINISHES
 SHALL COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION CHARACTERISTICS OF FINISHED TEXTILE FLOOR
 COVERING MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE,
 SHALL HAVE A MINIMUM CRITICAL RADIANT FLUX OF 0.1
 W/CM2.
 10.2.7.3* INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH 10.2.7.4, BASED ON TEST RESULTS FROM
 NFPA 253, STANDARD METHOD OF TEST FOR CRITICAL RADIANT
 FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT HEAT
 ENERGY SOURCE, OR ASTM E 648, STANDARD TEST METHOD FOR
 CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A
 RADIANT HEAT ENERGY SOURCE.
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED AS
 FOLLOWS IN ACCORDANCE WITH THEIR CRITICAL RADIANT FLUX
 VALUES:
 (1) CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
 (2) CLASS II INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.22 W/CM2 BUT LESS THAN 0.45 W/CM2, AS DETERMINED BY
 THE TEST DESCRIBED IN 10.2.7.3.
  
  
 PLEASE PROVIDE MANUFACTURES SPECIFICATION SHEETS THAT
 COMPLY WITH THE ABOVE CODES AND STANDARDS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709