| 2017-06-26 09:26:09 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FBC 107, THE TRANSMITTAL LETTER STATES THAT A |
| | NARRATIVE IS INCLUDED BUT I WAS UNABLE TO LOCATE A |
| | NARRATIVE FOR BUILDING, ONLY PLUMBING. DUE TO THE |
| | SIGNIFICANT NATURE OF THIS REVISION, AND DUE TO THE |
| | FACT THAT THE CHANGE AND THE REASON FOR THE CHANGE ARE |
| | NOT EASILY DETERMINED BY SOMEONE UNFAMILIAR WITH THE |
| | PROJECT, PLEASE PROVIDE A DETAILED NARRATIVE. |
| | |
| | 2. A101C, (AS AN EXAMPLE; APPLIES TO OTHER SHEETS) THE |
| | LAST REVIEWED SHEET WAS REVISION NO 20 DATED 9/30/16. |
| | THREE REVISIONS ARE SHOWN (28,29,30) AND NOT ALL |
| | CHANGES ARE CLOUDED. NARRATIVE SHOULD BE CLEAR AS TO |
| | CHANGES, CHANGES SHOULD BE INDICATED ON EACH PAGES. |
| | |
| | 2. FBC 2010 706.5.1, REVISE PLAN TO SHOW COMPLIANCE |
| | WITH ONE OF THE OPTIONS. THE PROPOSED NEW L-SHAPED 3 |
| | HOUR FIRE WALL INTERSECTS TWO EXTERIOR WALLS. |
| | |
| | 3. FBC 2010 706.5.2, REVISE PLAN TO INDICATE WHETHER OR |
| | NOT HORIZONTAL PROJECTION ELEMENTS ARE AFFECTED BY THIS |
| | CHANGE. |
| | |
| | 4. REVISE OTHER SHEETS AFFECTED BY THIS CHANGE; SUCH AS |
| | G001. |
| | |
| | 5. WALL ID TAGS DO NOT APPEAR TO HAVE BEEN REVISED TO |
| | REFLECT THE CHANGE FROM A 1 HOUR PARTITION OR BARRIER |
| | AND AN UNRATED WALL TO A 3 HOUR FIRE WALL. THE EXTERIOR |
| | PORTION OF THE PROPOSED NEW 3 HOUR FIRE WALL LACKS A |
| | WALL TAG, FBC 107, FBC 706. THE DETAIL FOR WALL TYPE N |
| | DOES NOT INCLUDE A 3 HOUR RATING, WALL TYPE P IS NOT A |
| | RATED WALL. REVISE DETAILS AND WALL TAGS TO SHOW A 3 |
| | HOUR WALL WHERE ONE IS PROPOSED. IT APPEARS THAT OTHER |
| | (PORTION OF) WALLS ALSO REQUIRE A RATING WHERE THEY |
| | INTERSECT THE 3 HOUR WALL, SEE OTHER COMMENTS. |
| | |
| | A102A, STAIR 1 SHOWS AN UNRATED WALL, ISN'T THIS AN |
| | EXIT STAIR WITH A 2 HOUR REQUIREMENT? STAIRS 1 AND 2 |
| | APPEAR TO SHOW A 0 RATING, BUT ELEVATOR 2-2 APPEARS TO |
| | SHOW A 2 HOUR REQUIREMNT. FBC 107, CLARIFY AND REVISE |
| | WALL ID TAGS AS NECESSARY. |
| | |
| | 6. PROVIDE A SUMMARY OF UNIT DESIGNATION NAME CHANGES |
| | (A COLUMN WITH THE OLD UNIT NUMBER, A COLUMN WITH THE |
| | CORRESPONDING NEW UNIT NUMBER), FBC 107. PAGES WHICH |
| | WERE AFFECTED BY THE CHANGE WHICH WERE NOT REVISED WILL |
| | BE COVERED UNDER THIS SUMMARY PAGE. |
| | |
| | |