| Plan Review Notes For Permit 17060340 |
| Permit Number |
17060340 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-15 07:21:39 | 1) THE GAS PERMIT APPLICATION STATES THAT THE GAS METER | | | IS EXISTING YET THE SURVEY AND THE WORK ORDER NOTES THE | | | METER AS NEW. CLARIFY. | | | 2) THE SURVEY SHOWS A BBQ WHICH I AM ASSUMING IS GAS | | | BUT THE GAS DRAWING DOES NOT SHOW THE BBQ. CLARIFY. | | | 3) SUBMIT A COPY OF THE LOW PRESSURE SIZING TABLE BEING | | | USED FOR THE SCH. 40 METALLIC PIPE OR REFERENCE THE | | | SPECIFIC SIZING TABLE ON BOTH SETS OF PLANS. 2014 FBCR | | | SEC.G2413.3. | | | 4) SHOW THE DISTANCE OF THE GENERATOR FROM THE | | | BUILDING.COMPLY WITH NFPA 37, SEC.4.1.2.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|