| Plan Review Notes For Permit 17060328 |
| Permit Number |
17060328 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-26 10:23:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. G101, THE PROPOSED NEW 3 HOUR WALL IS NOT SHOWN ON | | | THIS PLAN. REVISE TO INCLUDE, AND ALSO INCLUDE ANY | | | OTHER RATINGS REQUIRED DUE TO INTERSECTION, SEE | | | COMMENTS FOR 17060343. | | | | | | 2. IT IS NOT CLEAR WHAT CHANGED; PROVIDE A NARRATIVE OF | | | SIGNIFICANT CHANGES, FBC 107. | | | | | | 3. A105B, REVISE PLAN TO INCLUDE OCCUPANT LOAD FOR THE | | | OFFICE, FBC 1004, AND WHO WILL USE THIS OFFICE. REVISE | | | OTHER AFFECTED PAGES (SUCH AS CODE SUMMARY PAGE). | | | | | | OCCUPANT LOAD WAS ON THE PLAN, ADDED AS A RESULT OF A | | | PREVIOUS PLAN REVIEW COMMENT, AND WAS REMOVED. IT IS | | | NOT CLEAR WHY THIS WAS REMOVED; THIS IS REQUIRED TO | | | SHOW COMPLIANCE WITH THE ACCESSIBILITY EXEMPTION TO | | | VERTICAL ACCESSIBLITY. | | | | | | |
|