| Notes |
| Date |
Text |
| 2017-06-16 07:50:39 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060316 | | | 6/16/17 | | | | | | RESULTS: DENIED. | | | | | | 1) SHEETS MD100 & M100: THERE APPEAR TO BE MISSING FIRE | | | DAMPERS FOR THE DUCTS PENETRATING WHAT APPEAR TO BE | | | FIRE-RATED WALLS EMCOMPASSING ROOM 348- PLEASE CLARIFY. | | | | | | 2) THE MECHANICAL PLANS HAVE COPIED SEALS AND | | | SIGNATURES. THE ENGINEER OF RECORD CHAD A. WISLER SHALL | | | PROVIDE AN ORIGINAL SEAL WITH SIGNATURE AND DATE ON THE | | | MECHANICAL PLANS- SECTION 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|