| Plan Review Notes For Permit 17060278 |
| Permit Number |
17060278 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-29 16:59:59 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060278 | | | 6/29/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) A NON-COMBUSTIBLE DOOR IS REQUIRED FOR THE AC | | | CLOSET. SHEET A901 INDICATES A WOOD-LOUVERED DOOR- SEE | | | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION & SECTION | | | 602.2.1 FBC-14 MECHANICAL. | | | | | | 2) VERIFY THE O/A INTAKE OPENING IS IN COMPLIANCE WITH | | | SECTIONS 401.4 AND 401.5. | | | | | | 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE | | | NEW CONDENSER TO THE EXISTING AC ROOF STANDS. IF | | | SUBMITTING AN NOA PLEASE CIRCLE, HIGHLIGHT, OR | | | OTHERWISE MARK ALL APPLICABLE DESIGN PRESSURES, | | | DETAILS, AND FASTENERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|