| 2017-06-22 10:46:04 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION. THE CURRENT LOAD |
| | CALCULATION USES THE SMALLER OF THE NON-CONCURRENT |
| | LOAD, CODE REQUIRES THE USE OF THE LARGEST OF THE TWO |
| | LOADS. NEC 220.60 |
| | 2. PROVIDE DETAILS OF ALL CIRCUITS WIRED THROUGH THE |
| | LIGHTING CONTROL PANEL TO COMPLY WITH LIGHTING AND |
| | RECEPTACLE CONTROL PER THE NOTES ON PLAN. FBC 107.2.1 |
| | 3. PLAN SHOWS THAT BOTH ELECTRICAL ROOMS ARE FED FROM |
| | THE SAME MAIN, MAIN #5. PROVIDE LOAD CALCULATION FOR |
| | THE MAIN SERVICE TO SHOW SUFFICIENT SIZE FOR THE |
| | ADDITIONAL LOAD. NEC 220 |
| | 4. PROVIDE SHORT CIRCUIT CALCULATION AT |
| | METER/DISCONNECT TO CONFIRM AIC SIZING REQUIREMENT OF |
| | SERVICE EQUIPMENT. NEC 110.9, 110.10 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |