| | RESIDENTIAL (R3) ADDITION/ALTERATION 7TH BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: ON PREVIOUS REVIEWS THE PROVISO OPTION WAS |
| | OFFERED. UNFORTUNATELY, RE-SUBMITTALS ARE RAISING MORE |
| | QUESTIONS THAN ANSWERS, THEREFORE DELAYING THE PERMIT |
| | PROCESS. |
| | |
| | ENERGY CALCULATIONS SUBMITTED: |
| | 1- ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE |
| | BOTTOM OF THE FORM BY THE OWNER OR LEGALLY DESIGNATED |
| | AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | 2- HEATING AND COOLING INFORMATION SHOWN ON THE REVISED |
| | ENERGY CALCULATIONS DOESN'T MATCH INFORMATION SHOWN ON |
| | THE EQUIPMENT SIZING CALCULATIONS SUBMITTED. |
| | RESPONSE: REPEAT COMMENT. REVISE AS REQUIRED TO MATCH. |
| | |
| | 3- ON PREVIOUS REVIEW IT WAS REQUESTED TO SUBMIT THE |
| | COMPLETE ENERGY CALCULATIONS REPORT BECAUSE THEY WERE |
| | REVISED AND ONLY SOME PAGES WERE SUBMITTED. REPORT |
| | SUBMITTED NOW IS MISMATCHING PAGES FROM OLD REPORTS |
| | WITH PAGES OF THE LATEST REVISED REPORT. SOME PAGES ARE |
| | DATED 12/5/17 AND SOME PAGES ARE DATED 10/25/17. WHEN |
| | THERE ARE CHANGES A COMPLETE REPORT RUN ON THE SAME |
| | DATED NEED TO BE GENERATED. MISMATCHING PAGES IS NOT |
| | ALLOWED BECAUSE ANY CHANGE AFFECTS THE OVERALL REPORT. |
| | NOTE: INFORMATION SHOWN ON PAGE 3 OF 4 DATED 10/25/17 |
| | IS INCORRECT. FOR EXAMPLE THE WINDOWS INFORMATION |
| | DOESN'T MATCH PLANS. PROVIDE COMPLETE ENERGY |
| | CALCULATIONS REPORT THAT MATCHES PLANS TO AVOID MORE |
| | DELAYS OR CONFLICTS. |
| | |
| | 4- DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T MATCH |
| | PLANS. CLARIFY WHICH INSULATED DOORS ARE LOCATED EAST |
| | AND WEST. REVISE AS REQUIRED TO MATCH PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. NOTE: ONLY THE DOORS THAT SEPARATE A/C |
| | SPACE FROM NON A/C SPACE ARE TO BE CONSIDERED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |