| 2017-11-29 08:01:56 | RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO: PROVISO |
| | MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED REVISED |
| | INFORMATION AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY |
| | INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR TO |
| | ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS TIME. |
| | REVISION FEES APPLY IF INFORMATION IS SUBMITTED AFTER |
| | THE PERMIT IS ISSUED. |
| | |
| | NEW COMMENT: |
| | 1- A) EQUIPMENT SIZE SPECIFIED ON THE A/C PLAN |
| | SUBMITTED DOESN'T MATCH EQUIPMENT SIZE SPECIFIED ON THE |
| | ENERGY CALCULATIONS SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B) EQUIPMENT SPECIFIED ON THE A/C PLAN SUBMITTED |
| | DOESN'T MATCH EQUIPMENT SPECIFIED ON THE EQUIPMENT |
| | SIZING CALCULATIONS SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | |
| | 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED |
| | ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION |
| | OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | |
| | 3- ARCHITECT OF RECORD TO SIGN AND SEAL BOTH A/C PLANS |
| | SUBMITTED AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE |
| | WHEN SUBMITTING PLANS FOR PUBLIC RECORDS. NOTE: ONLY |
| | ONE COPY WAS SIGNED AT THIS TIME. |
| | |
| | |
| | NOTE: CONTRACTOR MAY PROVIDE COMPLETE INFORMATION UNDER |
| | A SEPARATE MECHANICAL PERMIT. ADVICE IF THIS OPTION IS |
| | PREFERRED AT HIS TIME. |
| | |
| | |
| | *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |