| 2017-06-12 11:36:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 1) THE INSTALL SHALL MEET THE MINIMUM DECIBEL LEVELS AT |
| | THE PILLOW HEIGHT IN EACH ROOM. |
| | |
| | 18.4.5 SLEEPING AREA REQUIREMENTS. |
| | 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO |
| | PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A |
| | SOUND LEVEL OF AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT |
| | SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL |
| | HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND |
| | LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER, |
| | MEASURED AT THE PILLOW LEVEL IN THE AREA REQUIRED TO BE |
| | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). |
| | 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR |
| | RETRACTABLE PARTITION, IS LOCATED BETWEEN THE |
| | NOTIFICATION APPLIANCE AND THE PILLOW, THE SOUND |
| | PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER |
| | PLACED BETWEEN THE APPLIANCE AND THE PILLOW. |
| | 18.4.5.3* EFFECTIVE JANUARY 1, 2014, WHERE AUDIBLE |
| | APPLIANCES ARE PROVIDED TO PRODUCE SIGNALS FOR SLEEPING |
| | AREAS, THEY SHALL PRODUCE A LOW FREQUENCY ALARM SIGNAL |
| | THAT COMPLIES WITH THE FOLLOWING: |
| | (1) THE ALARM SIGNAL SHALL BE A SQUARE WAVE OR PROVIDE |
| | EQUIVALENT AWAKENING ABILITY. |
| | (2) THE WAVE SHALL HAVE A FUNDAMENTAL FREQUENCY OF 520 |
| | HZ ? 10 PERCENT |
| | |
| | |