| 2017-06-21 13:02:23 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | COMPLY WITH ZONING AND FIRE COMMENT FOR AN ELECTRICAL |
| | PLAN REVIEW. |
| 2017-06-21 09:26:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE IS NOT SITE PLAN SUBMITTED SHOWING THE |
| | LOCATION OF THE GENERATOR WITH DIMESIONS TO ALL |
| | INPORTANT BUILDINGS AND STRUCTURES AND TO CONFIRM ITS |
| | LOCATION. |
| | |
| | PLEASE PROVIDE A DETAILED SITE PLAN. |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION IF THIS GENERATOR SUPPLIES |
| | EMERGENCY POWER TO THE LIFE SAFETY SYSTEMS OF THE |
| | STRUCTURES IT SERVES. IF SO, THE INSTALLATION SHALL |
| | COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY AND |
| | STANDBY POWER SYSTEMS. |
| | |
| | THIS STANDARD COVERS PERFORMANCE REQUIREMENTS FOR |
| | EMERGENCY AND STANDBY POWER SYSTEMS PROVIDING AN |
| | ALTERNATE SOURCE OF ELECTRICAL POWER IN BUILDINGS AND |
| | FACILITIES IN THE EVENT THAT THE NORMAL ELECTRICAL |
| | POWER SOURCE FAILS. SYSTEMS INCLUDE POWER SOURCES, |
| | TRANSFER EQUIPMENT, CONTROLS, SUPERVISORY EQUIPMENT, |
| | AND ACCESSORY EQUIPMENT NEEDED TO SUPPLY ELECTRICAL |
| | POWER TO THE SELECTED CIRCUITS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | COMPLIANCE. |
| | |
| | |
| | 3) SHOULD # 2 APPLY, PLEASE PROVIDE HOW THE LIFE SAFETY |
| | SYSTEMS WILL BE MAINTAINED AND MONITORED DURING THE |
| | SWITCH OVER TO THE NEW ONE. |
| | |
| | HOW LONG WILL THE SWITCH OVER TAKE? WILL A FIRE WATCH |
| | BE IMPLEMENTED? BY WHOM? WILL A TEMPORARY GENERATOR BE |
| | INSTALLED? ETC.... |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |