Plan Review Notes
Plan Review Notes For Permit 17060241
Permit Number 17060241
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-13 15:23:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) UNDER THE LIFE SAFETY COMPLIANCE ANALYSIS, NOTES,
 THERE IS AN INCORRECT REFERENCE TO THE FIRE CODE; NFPA
 101 - 42.2.4.1. THIS CHAPTER PERTAINS TO STORAGE
 OCCUPANCIES.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
  
  
 2) UNDER THE FIRE NOTE BOX THERE IS AN INCORRECT
 REFERENCE INDICATING "ALL EXITS SHALL COMPLY WITH NFPA
 101 - 14." THE MEANS OF EGRESS CHAPTER IN NFPA 101 IS
 CHAPTER 7.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
  
  
 3) THERE IS NO DRAWING DEPICITING THE HORIZONTAL VIEW
 OF THE PROPOSED INSTALLATION SHOWING DIMENSIONS FROM
 WINDOWSOR OTHER OPENINGS.
  
 PLEASE PROVIDE WITH DETAILS.
  
  
  
 4) THERE IS A DRAWING OF "TYP. ACCESSIBLE DOOR";
 HOWEVER, THE FLOOR DRAWING INDICATES EXISTING EGRESS
 WINDOW.
  
 THERE IS NO DOOR SCHEDULE INCLUDING HARDWARE AND
 LATCHING LOCKING DETAILS.
  
 THERE IS NO INDICATION OF HOW TO OPEN AND/OR OPERATE
 THE EXISTING WINDOWS.
  
 PLEASE REVIEW AND CLARIFY.
  
  
  
 5) THE PROPOSED INSTALLATION DOES NOT MEET THE
 REQUIREMENTS OF NFPA CHAPTER 31, EXISTING APARTMENT
 BUILDINGS AND CAN NOT BE USED AS A MEANS OF EGRESS.
  
 31.2.2.10 FIRE ESCAPE LADDERS. FIRE ESCAPE LADDERS
 COMPLYING WITH 7.2.9 SHALL BE PERMITTED.
  
 7.2.9 FIRE ESCAPE LADDERS.
 7.2.9.1 GENERAL. FIRE ESCAPE LADDERS COMPLYING WITH
 7.2.9.2 AND
 7.2.9.3 SHALL BE PERMITTED IN THE MEANS OF EGRESS ONLY
 WHERE PROVIDING ONE OF THE FOLLOWING:
  
 (1) ACCESS TO UNOCCUPIED ROOF SPACES AS PERMITTED IN
 7.2.8.3.4
 (2) SECOND MEANS OF EGRESS FROM STORAGE ELEVATORS AS
 PERMITTED IN CHAPTER 42
 (3) MEANS OF EGRESS FROM TOWERS AND ELEVATED PLATFORMS
 AROUND MACHINERY OR SIMILAR SPACES SUBJECT TO OCCUPANCY
 NOT TO EXCEED THREE PERSONS WHO ARE ALL CAPABLE OF
 USING THE LADDER
 (4) SECONDARY MEANS OF EGRESS FROM BOILER ROOMS OR
 SIMILAR SPACES SUBJECT TO OCCUPANCY NOT TO EXCEED THREE
 PERSONS WHO ARE ALL CAPABLE OF USING THE LADDER
 (5) ACCESS TO THE FINISHED GROUND LEVEL FROM THE LOWEST
 BALCONY OR LANDING OF A FIRE ESCAPE STAIR FOR SMALL
 BUILDINGS AS PERMITTED IN 7.2.8.4 WHERE APPROVED BY THE
 AUTHORITY HAVING JURISDICTION
  
  
 7.2.9.2 CONSTRUCTION AND INSTALLATION.
 7.2.9.2.1 FIRE ESCAPE LADDERS SHALL COMPLY WITH ANSI
 A14.3, SAFETY REQUIREMENTS FOR FIXED LADDERS, UNLESS
 ONE OF THE FOLLOWING CRITERIA IS MET:
 (1) APPROVED EXISTING LADDERS COMPLYING WITH THE
 EDITION OF THIS CODE THAT WAS IN EFFECT WHEN THE
 LADDERS WERE INSTALLED SHALL BE PERMITTED.
 (2) INDUSTRIAL STAIRS COMPLYING WITH THE MINIMUM
 REQUIREMENTS FOR FIXED STAIRS OF ANSI/ASSE A1264.1,
 SAFETY REQUIREMENTS FOR WORKPLACE FLOOR AND WALL
 OPENINGS, STAIRS AND RAILING SYSTEMS, SHALL BE
 PERMITTED WHERE FIRE ESCAPE LADDERS ARE PERMITTED IN
 ACCORDANCE WITH CHAPTER 40.
 7.2.9.2.2 LADDERS SHALL BE INSTALLED WITH A PITCH THAT
 EXCEEDS 75 DEGREES.
 7.2.9.3 ACCESS. THE LOWEST RUNG OF ANY LADDER SHALL NOT
 BE MORE THAN 12 IN. (305 MM) ABOVE THE LEVEL OF THE
 SURFACE BENEATH IT.
  
 PLEASE REIVEW AND PROVIDE DRAWINGS AND DESIGN THAT MEET
 THE REQUIREMENTS OF NFPA 101, CHAPTER 31 AND CHAPTER 7.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  