| Plan Review Notes For Permit 17060241 |
| Permit Number |
17060241 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-07 12:58:54 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. APPLICATION IS DENIED BASED ON FBC EXISTING BUILDING | | | CODE CHAPTER 604.1 "MEANS OF EGRESS". REPAIRS SHALL BE | | | DONE IN A MANNER THAT MAINTAINS THE LEVEL OF PROTECTION | | | PROVIDED FOR THE MEANS OF EGRESS. | | | 502.1 SCOPE. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE | | | THE PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED | | | MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE | | | PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND | | | CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE | | | REQUIREMENTS. | | | | | | 2. EXISTING EGRESS WAS PROVIDED BY AN EXTERIOR DOOR | | | LEADING TO A LANDING AND EXIT STAIRS. | | | | | | 3. PROPOSED FIRE ESCAPE REQUIRES EXIT THROUGH A WINDOW | | | (NO DETAILS PROVIDED) ONTO A LANDING THEN CLIMBING DOWN | | | A LADDER ATTACHED TO THE EXTERIOR WALL. | | | | | | 4. PLAN SUBMITTED DOES NOT SHOW EXISTING EXTERIOR | | | DOORS. ARCHITECT TO VISIT SITE TO REVIEW IN-PLACE | | | BUILDING ELEMENTS. | | | | | | 5. NO RECORD OF PERMIT APPLICATION TO REMOVE EXTERIOR | | | DOORS. | | | |
|