2017-07-07 12:58:54BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. APPLICATION IS DENIED BASED ON FBC EXISTING BUILDING
 CODE CHAPTER 604.1 "MEANS OF EGRESS". REPAIRS SHALL BE
 DONE IN A MANNER THAT MAINTAINS THE LEVEL OF PROTECTION
 PROVIDED FOR THE MEANS OF EGRESS.
 502.1 SCOPE. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE
 THE PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED
 MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE
 PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND
 CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE
 REQUIREMENTS.
  
 2. EXISTING EGRESS WAS PROVIDED BY AN EXTERIOR DOOR
 LEADING TO A LANDING AND EXIT STAIRS.
  
 3. PROPOSED FIRE ESCAPE REQUIRES EXIT THROUGH A WINDOW
 (NO DETAILS PROVIDED) ONTO A LANDING THEN CLIMBING DOWN
 A LADDER ATTACHED TO THE EXTERIOR WALL.
  
 4. PLAN SUBMITTED DOES NOT SHOW EXISTING EXTERIOR
 DOORS. ARCHITECT TO VISIT SITE TO REVIEW IN-PLACE
 BUILDING ELEMENTS.
  
 5. NO RECORD OF PERMIT APPLICATION TO REMOVE EXTERIOR
 DOORS.
  