Plan Review Notes
Plan Review Notes For Permit 17060236
Permit Number 17060236
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-12 08:09:33****CORRECTIONS****
 REVISED 6/23/17
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE ENERGY CALCS; VERY LITTLE DATA IN THE DATA ENTRY
 REPORT - NO FLOOR, EXT. LIGHTING, WINDOWS, ROOF, DOORS,
 WALLS, ETC. CLARIFY OR REVISE, FBC 107.
  
 2. FBC B 1004, A-1.0, REVISE PROJECT INFORMATION TO
 INCLUDE SQUARE FOOT AREA FOR THIS SPACE, SQUARE FEET
 PER PERSON.
  
 3. FBC A 604.8.1, REVISE PLAN TO SHOW OVERALL SIZE OF
 ACCESSIBLE COMPARTMENT, FBC A FIGURE 604.8.1.6 SHOW
 TURNING RADIUS REQUIRED. PLAN APPEARS TO COMPLY; REVISE
 TO DEMONSTRATE COMPLIANCE AND FIELD REQUIREMENT.
  
 4. FBC A 604.8.1.2, THE TOILET COMPARTMENT DOOR IS TO
 BE SELF CLOSING, REVISE PLAN TO INDICATE REQUIREMENT.
  
 5. 6/23/17 - FBC COURSE - OK (RECEIVED VIA EMAIL,
 FORWARDED TO FBPE)
  
  
  
  