| 2017-06-12 08:09:33 | ****CORRECTIONS**** | | | REVISED 6/23/17 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SEE ENERGY CALCS; VERY LITTLE DATA IN THE DATA ENTRY | | | REPORT - NO FLOOR, EXT. LIGHTING, WINDOWS, ROOF, DOORS, | | | WALLS, ETC. CLARIFY OR REVISE, FBC 107. | | | | | | 2. FBC B 1004, A-1.0, REVISE PROJECT INFORMATION TO | | | INCLUDE SQUARE FOOT AREA FOR THIS SPACE, SQUARE FEET | | | PER PERSON. | | | | | | 3. FBC A 604.8.1, REVISE PLAN TO SHOW OVERALL SIZE OF | | | ACCESSIBLE COMPARTMENT, FBC A FIGURE 604.8.1.6 SHOW | | | TURNING RADIUS REQUIRED. PLAN APPEARS TO COMPLY; REVISE | | | TO DEMONSTRATE COMPLIANCE AND FIELD REQUIREMENT. | | | | | | 4. FBC A 604.8.1.2, THE TOILET COMPARTMENT DOOR IS TO | | | BE SELF CLOSING, REVISE PLAN TO INDICATE REQUIREMENT. | | | | | | 5. 6/23/17 - FBC COURSE - OK (RECEIVED VIA EMAIL, | | | FORWARDED TO FBPE) | | | | | | | | | | | | |
|