| Plan Review Notes For Permit 17060234 |
| Permit Number |
17060234 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-09-26 07:01:00 | PROVISO: | | | THESE CORRECTIONS SHALL BE MADE ON REVISED SHEETS PRIOR | | | TO 1ST ROUGH INSPECTION. | | | 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | | THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT | | | SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT | | | VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL | | | OR WASTE. PER FBC PL 914.2 | | | 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB | | | AMEND TO FBC 107.2.1 | | | 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ | | | AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE | | | EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | |
|