Plan Review Notes
Plan Review Notes For Permit 17060234
Permit Number 17060234
Review Stop P
Sequence Number 3
Notes
Date Text
2017-09-26 07:01:00PROVISO:
 THESE CORRECTIONS SHALL BE MADE ON REVISED SHEETS PRIOR
 TO 1ST ROUGH INSPECTION.
 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT
 SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT
 VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL
 OR WASTE. PER FBC PL 914.2
 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB
 AMEND TO FBC 107.2.1
 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ
 AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE
 EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  