2017-08-24 15:15:441ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT
 SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT
 VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL
 OR WASTE. PER FBC PL 914.2
  
 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ
 AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE
 EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  