Plan Review Notes
Plan Review Notes For Permit 17060234
Permit Number 17060234
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-08-28 14:24:402ND REVIEW COMMENTS
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS REVIEW AND THE COMMENTS ARE RELATED TO THE
 FOUNDATION PERMIT ONLY.
  
  
 1) SHEET 2 OF 8 - THERE ARE NO INDICATION HOW THE
 EXISTING REQUIRED EXITING, INCLUDING WALKWAY AND
 STAIRS, WILL BE MAINTAINED DURING DEMO AND ALL PHASES
 OF CONSTRUCTION.
  
 NOT COMPLIED. YOUR COMMENTS THAT A DETAILED LIFE SAFETY
 PLAN WAS SUBMITTED COULD NOT BE FOUND.
  
 THE LIFE SAFETY PLAN SHALL INCLUDED THE EXIT PATH FROM
 ALL SOUTH END EXITS, INCLUDING THE STAIRS FROM THE 2 ND
 FL, THE TRAVEL PATH LEADING TO A POINT OF PUBLIC WAY,
 THESE PLANS SHALL INCLUDE EXIT WIDTH, ELEVATION
 CHANGES, EXIT SIGNAGE, SEPARATION MEASURES FROM
 CONSTRUCTION.
  
 THESE ITEMS WERE DISCUSSED AT LENGTH DURING A MEETING
 WITH THE AHRENS TEAM.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN INDICATING
 HOW AND WHERE THE EXITING FROM THE CURRENT BUILDING
 WILL BE MAINTAINED AND PROTECTED.
  
  
  
  
 2) SHEET 7 OF 8 - THE FIRE LINE APPEARS TO BE UNDER THE
 FOUNDATION. PER NFPA 24 THIS IS A VIOLATION OF THE
 REQUIRERMENT.
  
 NOT COMPLIED. THERE IS NO DRAWING OR NOTE THAT SAYS THE
 FIRE LINE BEING MOVED.
  
 ADDITIONALLY, IT SHALL BE NOTED ON THE RESUBMITTAL THAT
 ALL UNDERGROUND WORK SHALL COMPLY WITH NFPA 24,
 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES, 2010 EDITION.AND BE DONE
 UNDER SEPARATE PERMIT BY CERTIFIED FLORIDA UNDERGROUND
 CONTRACTORS. NO FIRE LINE PIPE SHALL BE COVERED OVER
 PRIOR TO A FIRE INSPECTION.
  
 10.6 PROTECTION AGAINST DAMAGE.
 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS.
 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL
 PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING:
 (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE
 (2) RUNNING PIPE IN COVERED TRENCHES
 (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER
 BUILDINGS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  