| 2017-08-23 11:13:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NEW SUBMISSION SHOWS MODIFICATIONS TO THE EXISTING |
| | SERVICE. PROVIDE CLARIFICATION. IS THIS SERVICE AT A |
| | DIFFERENT ADDRESS, REQUIRING A SEPARATE PERMIT? WHY IS |
| | PANEL K BEING ADDED? PANEL K AND THE EXISTING SERVICE |
| | ARE NOT SHOWN ON POWER PLAN SUBMITTED, WHAT IS THE |
| | LOCATION OF THESE ITEMS? PROVIDE LOAD CALCULATION FOR |
| | EXISTING SERVICE AND JUSTIFICATION FOR INCREASE (?) IN |
| | SIZE. PROVIDE NOTE FOR ANY SEPARATE PERMITS REQUIRED. |
| | FBC 107.2.1 |
| | |
| | BECAUSE THIS IS FOR A FOUNDATION PERMIT ONLY, THIS IS |
| | THE ONLY QUESTION AT THIS TIME. WHEN A FULL PLAN REVIEW |
| | IS COMPLETED FOR THE MASTER PERMIT, ADDITIONAL COMMENTS |
| | WILL BE FORTHCOMING. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |