| Plan Review Notes For Permit 17060234 |
| Permit Number |
17060234 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-19 10:26:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS REVIEW AND THE COMMENTS ARE RELATED TO THE | | | FOUNDATION PERMIT ONLY. | | | | | | | | | 1) SHEET 2 OF 8 - THERE ARE NO INDICATION HOW THE | | | EXISTING REQUIRED EXITING, INCLUDING WALKWAY AND | | | STAIRS, WILL BE MAINTAINED DURING DEMO AND ALL PHASES | | | OF CONSTRUCTION. | | | | | | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN INDICATING | | | HOW AND WHERE THE EXITING FROM THE CURRENT BUILDING | | | WILL BE MAINTAINED AND PROTECTED. | | | | | | | | | | | | | | | 2) SHEET 7 OF 8 - THE FIRE LINE APPEARS TO BE UNDER THE | | | FOUNDATION. PER NFPA 24 THIS IS A VIOLATION OF THE | | | REQUIRMENT. | | | | | | 10.6 PROTECTION AGAINST DAMAGE. | | | 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS. | | | 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL | | | PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING: | | | (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE | | | (2) RUNNING PIPE IN COVERED TRENCHES | | | (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER | | | BUILDINGS | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|