Plan Review Notes
Plan Review Notes For Permit 17060222
Permit Number 17060222
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-10-03 16:20:3310/04/2017
  
 PASS WITH PROVISO COMMENTS:
  
 FFPC 1.14.4 REVIEW AND APPROVAL SHALL NOT RELIEVE THE
 APPLICANT OF THE RESPONSIBILITY OF COMPLIANCE WITH THE
 CODE.
  
 TRASH CHUTE SPECIFICATION /CUT SHEET REQUIRED. CHUTE
 TERMINATION FLOOR, WILL THERE BE A FUSIBLE LINK TO
 CLOSE THE CHUTE AND FIRE SPRINKLER HEAD TO PROTECT THE
 TRASH DUMPSTER. SUBMIT DETAIL DRAWINGS AND PROVIDE
 PLANS ON JOB SITE.
  
 TRASH CHUTE INSTALLATION SHALL COME INTO COMPLIANCE
 WITH NFPA 82.
  
 STANDPIPE # 2, DETAIL INDICATES NO PSI GAUGE. PROVIDE
 PSI GAUGE.
  
 NOTE: PRV WILL BE SET AND TAGGED FROM THE FACTORY.
  
 THESE CODES ARE MINIMUM REQUIREMENTS ALL INSTALLATION
 SHALL COMPLY WITH NFPA 13, 14 STATE AND LOCAL CODES.
 ONSITE INSPECTIONS AND VERIFICATIONS BY A FIRE
 PREVENTION BUREAU INSPECTOR MAY NECESSITATE
 ADJUSTMENTS, ADDITIONS, RELOCATIONS, PERFORMANCE
 TESTING AND/OR OTHER APPLICATION DIMENSION TO MEET THE
 LIFE SAFETY COMPLIANCE CRITERIA.
  