| Plan Review Notes For Permit 17060222 |
| Permit Number |
17060222 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-10-03 16:20:33 | 10/04/2017 | | | | | | PASS WITH PROVISO COMMENTS: | | | | | | FFPC 1.14.4 REVIEW AND APPROVAL SHALL NOT RELIEVE THE | | | APPLICANT OF THE RESPONSIBILITY OF COMPLIANCE WITH THE | | | CODE. | | | | | | TRASH CHUTE SPECIFICATION /CUT SHEET REQUIRED. CHUTE | | | TERMINATION FLOOR, WILL THERE BE A FUSIBLE LINK TO | | | CLOSE THE CHUTE AND FIRE SPRINKLER HEAD TO PROTECT THE | | | TRASH DUMPSTER. SUBMIT DETAIL DRAWINGS AND PROVIDE | | | PLANS ON JOB SITE. | | | | | | TRASH CHUTE INSTALLATION SHALL COME INTO COMPLIANCE | | | WITH NFPA 82. | | | | | | STANDPIPE # 2, DETAIL INDICATES NO PSI GAUGE. PROVIDE | | | PSI GAUGE. | | | | | | NOTE: PRV WILL BE SET AND TAGGED FROM THE FACTORY. | | | | | | THESE CODES ARE MINIMUM REQUIREMENTS ALL INSTALLATION | | | SHALL COMPLY WITH NFPA 13, 14 STATE AND LOCAL CODES. | | | ONSITE INSPECTIONS AND VERIFICATIONS BY A FIRE | | | PREVENTION BUREAU INSPECTOR MAY NECESSITATE | | | ADJUSTMENTS, ADDITIONS, RELOCATIONS, PERFORMANCE | | | TESTING AND/OR OTHER APPLICATION DIMENSION TO MEET THE | | | LIFE SAFETY COMPLIANCE CRITERIA. | | | | | | FRANK STALLWORTH, FIRE INSPECTOR I | | | WEST PALM BEACH FIRE PREVENTION BUREAU | | | 500 N. DIXIE HWY | | | WEST PALM BEACH, FLORIDA 33401 | | | OFFICE: 561-840-4780 | | | FAX: 561-840-4774 | | | [email protected] | | | | | | | | | |
|