2017-06-22 17:21:08NFPA 1-14.2, 2012 THE APPLICANT SHALL BE RESPONSIBLE TO
 ENSURE THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
  
 PROVIDE FIRE SPRINKLER ISOMETRIC PLAN, FOR TRASH
 CHUTES. INSTALLATIONS SHALL COME IN COMPLIANCE WITH
 NFPA 13 AND 82-5.2.6.1. ALSO INDICATE WHAT FLOOR CHUTE
 TERMINATES. 82-5.2.6.1, 2009 EDITION GRAVITY CHUTE.
 5.2.6.1.1 GRAVITY CHUTES SHALL BE PROTECTED INTERNALLY
 BY AUTOMATIC SPRINKLERS.
 5.2.6.1.2 THIS PROTECTION REQUIRES THAT A SPRINKLER BE
 INSTALLED AT OR ABOVE THE TOP SERVICE OPENING OF THE
 CHUTE.
 5.2.6.1.3 THIS PROTECTION REQUIRES AUTOMATIC SPRINKLERS
 INSTALLED IN GRAVITY CHUTE SERVICE OPENINGS SHALL BE
 RECESSED OUT OF THE CHUTE AREA THROUGH WHICH THE
 MATERIAL TRAVELS.
 5.2.6.1.4 IN ADDITION, A SPRINKLER SHALL BE INSTALLED
 WITHIN THE CHUTE AT ALTERNATE FLOOR LEVELS IN BUILDINGS
 OVER TWO STORIES IN HEIGHT, WITH A MANDATORY SPRINKLER
 LOCATED AT THE LOWEST SERVICE LEVEL.
 NFPA 13-6.2.8, 2010: SPRINKLERS SUBJECT TO MECHANICAL
 INJURY SHALL BE PROTECTED WITH LISTED GUARDS. PROVIDE
 CUT SHEET FOR GUARDS, PROVIDE GUARDS IN MECHANICAL
 ROOMS, ELECTRICAL ROOMS AND OTHER AREA PER CODE.
 FP -03 LEVEL 1: FIRE SPRINKLER HEADS IN GENERATOR ROOM
 INDICATE VIKING 155 DEGREE FIRE SPRINKLER TYPE HEAD;
 HEADS MAY REQUIRE HIGHER TEMPERATURE FOR ENVIRONMENT.
 LEVEL P-2: CLARIFICATION FIRE SPRINKLER PROTECTION IN
 ELEVATOR PITS?
 P-1 ADDITIONAL FIRE SPRINKLER PROTECTION SHALL BE
 REQUIRED, IF PRIVATE GARAGE INSTALL VEHICLE LIFTS.
 INSTALLATION SHALL COME IN COMPLIANCE WITH NFPA 13 AND
 13-NFPA 13-8.10.6.3, OBSTRUCTIONS THAT PREVENT
 SPRINKLER DISCHARGE FROM REACHING THE HAZARD.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU