| 2017-06-12 10:48:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP 201 A - THERE IS A NOTE IN THE UPS ROOM, |
| | 193 AND IM, 109, INDICATING "ANSUL SAPPHIRE SYSTEM TO |
| | BE PROVIDED BY OTHERS". |
| | |
| | PER NFPA 13, |
| | |
| | 8.15.10 ELECTRICAL EQUIPMENT. |
| | 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET, |
| | SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL |
| | EQUIPMENT ROOMS. |
| | 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT |
| | IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE |
| | SHALL BE NONCOMBUSTIBLE. |
| | 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN |
| | ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY. |
| | (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED. |
| | (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED |
| | ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS. |
| | (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN |
| | THE ROOM. |
| | |
| | |
| | PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL |
| | OF REQUIRED CONDITIONS. |
| | |
| | IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION. |
| | SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY |
| | SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM |
| | MAY BE CONSIDERED. |
| | |
| | |
| | 2) SHEET FP 202, 202 A & 202 B - THERE IS A NOTE IN THE |
| | IM ROOM, 233, INDICATING "ANSUL SAPPHIRE SYSTEM TO BE |
| | PROVIDED BY OTHERS". |
| | |
| | PER NFPA 13, |
| | |
| | 8.15.10 ELECTRICAL EQUIPMENT. |
| | 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET, |
| | SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL |
| | EQUIPMENT ROOMS. |
| | 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT |
| | IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE |
| | SHALL BE NONCOMBUSTIBLE. |
| | 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN |
| | ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY. |
| | (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED. |
| | (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED |
| | ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS. |
| | (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN |
| | THE ROOM. |
| | |
| | |
| | PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL |
| | OF REQUIRED CONDITIONS. |
| | |
| | IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION. |
| | SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY |
| | SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM |
| | MAY BE CONSIDERED. |
| | |
| | |
| | |
| | 3) SHEET FP 200 - THERE IS AN INDICATION WITHIN THE |
| | CALC AREA B BOX OF 1589 SQ. FT.. THIS INDICATIONDOES |
| | NOT MATCH THE SQ. FT. INDICATION ON SHEET FP 202 B OR |
| | THE HYDRALIC CALCULATION SUBMITTAL. |
| | |
| | PLEASE REVIEW AND CLRIFY OR CORRECT. |
| | |
| | |
| | |
| | 4) SHEET FP 202 B - THERE IS AN INCORRECT FIRE CODE |
| | EDITION (07) REFERENCE WITH THE DESIGN AREA REDUCTION |
| | CALL OUT INFORMATION. |
| | |
| | PLEASE CORRECT TO THE CURRENT, 2010 EDITION, OF NFPA |
| | 13. |
| | |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |