Date Text
2017-06-12 10:48:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 201 A - THERE IS A NOTE IN THE UPS ROOM,
 193 AND IM, 109, INDICATING "ANSUL SAPPHIRE SYSTEM TO
 BE PROVIDED BY OTHERS".
  
 PER NFPA 13,
  
 8.15.10 ELECTRICAL EQUIPMENT.
 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET,
 SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL
 EQUIPMENT ROOMS.
 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE
 SHALL BE NONCOMBUSTIBLE.
 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE ROOM.
  
  
 PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL
 OF REQUIRED CONDITIONS.
  
 IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
 SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY
 SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM
 MAY BE CONSIDERED.
  
  
 2) SHEET FP 202, 202 A & 202 B - THERE IS A NOTE IN THE
 IM ROOM, 233, INDICATING "ANSUL SAPPHIRE SYSTEM TO BE
 PROVIDED BY OTHERS".
  
 PER NFPA 13,
  
 8.15.10 ELECTRICAL EQUIPMENT.
 8.15.10.1 UNLESS THE REQUIREMENTS OF 8.15.10.3 ARE MET,
 SPRINKLER PROTECTION SHALL BE REQUIRED IN ELECTRICAL
 EQUIPMENT ROOMS.
 8.15.10.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE
 SHALL BE NONCOMBUSTIBLE.
 8.15.10.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT ROOMS WHERE ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE ROOM.
  
  
 PLEASE PROVIDED DOCUMENTATION THAT THIS ROMM MEETS ALL
 OF REQUIRED CONDITIONS.
  
 IF NOT, PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
 SHOULD A WET SYSTEM NOT BE THE PREFERRED SYSTEM, A DRY
 SYSTEM WITH PREACTION THAT BACKS UP THE ANSUL SYSTEM
 MAY BE CONSIDERED.
  
  
  
 3) SHEET FP 200 - THERE IS AN INDICATION WITHIN THE
 CALC AREA B BOX OF 1589 SQ. FT.. THIS INDICATIONDOES
 NOT MATCH THE SQ. FT. INDICATION ON SHEET FP 202 B OR
 THE HYDRALIC CALCULATION SUBMITTAL.
  
 PLEASE REVIEW AND CLRIFY OR CORRECT.
  
  
  
 4) SHEET FP 202 B - THERE IS AN INCORRECT FIRE CODE
 EDITION (07) REFERENCE WITH THE DESIGN AREA REDUCTION
 CALL OUT INFORMATION.
  
 PLEASE CORRECT TO THE CURRENT, 2010 EDITION, OF NFPA
 13.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  