2018-05-23 08:40:464TH REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17060212
 5/22/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE FOLLOWING REVIEW IS BASED ON THE NEW MECHANICAL
 PLANS AND SPECIFICATIONS SUBMITTED. THE VOIDED PLANS
 WERE NOT RETURNED WITH THE NEW PLAN SHEETS.
  
 1) SHEET M-2: THE RETURN TRANSFER DUCTS FROM THE
 BEDROOMS ARE UNDERSIZED PER SECTION M1602.4 ITEMS 1 & 2
 FBC-14 RESIDENTIAL. BECASUE ALL BEDROOMS ARE MASTER
 SUITES CONTAINING BATHS AND CLOSET, AND EACH IS BEING
 SUPPLIED BY A 16" X 10" DUCT, THEN EACH WILL REQUIRE A
 TRANSFER DUCT WITH A MINIMUM CROSS SECTION AREA OF 240
 SQ. INCHES,
  
 2) THE SUBMITTAL FOR THE EXHAUST HOOD INDICATES A
 MAXIMUM EXHAUST RATE OF 900 CFMS WHICH WILL REQUIRE
 MAKEUP AIR TO BE PROVIDED PER SECTION M1503.4. THE
 MAKEUP AIR SYSTEM SHALL BE EQUIPPED WITH A MEANS OF
 CLOSURE, AND SHALL BE AUTOMATICALLY CONTROLLED TO START
 AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 3) THE AHRI CERTIFICATES DO NOT MATCH WITH THE NEW 4
 AND 2.5-TON AC SYSTEMS SELECTED AND SHOWN IN THE
 SCHEDULES ON M-2.
  
 4) THE RESCHECK ENERGY EFFICIENCY CERTIFICATE DOES NOT
 PROVIDE ANY COMPLIANCE DATA FOR THE AC SYSTEMS OR THE
 WATER HEATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  