| 2017-11-03 15:36:36 | FOUR TIMES FEE FOR PLAN REVIEW ADDED, SEE BELOW. |
| | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | PLEASE READ COMMENTS IN THEIR ENTIRETY AND RESPOND TO |
| | ALL ITEMS. THERE ARE A TOTAL OF 7 COMMENTS. THE |
| | RESPONSE LETTER PROVIDED STATED THE PREVIOUS COMMENTS |
| | WERE ADDRESSED, BUT THE FOLLOWING ITEMS REMAIN |
| | INCORRECT. |
| | |
| | 1. PREVIOUS COMMENT # 10. PROVIDE CARBON MONOXIDE |
| | ALARMS AS REQUIRED PER CODE. FBC RE315.1 CO ALARMS ARE |
| | REQUIRED WITHING 10 FEET OF EACH SLEEPING AREA. SEE |
| | REFERENCED CODE AND PROVIDE CORRECTION. FBC R315.1 |
| | 2. PREVIOUS COMMENT # 11. SHOW GFCI PROTECTED OUTLET |
| | FOR GARAGE DOOR OPENER. NEC 210.8; FBC RE3902.2 |
| | 3. PREVIOUS COMMENT # 12. 400 AMP SERVICE IS SHOWN WITH |
| | 3/0 WIRE FEEDING THE SERVICE. 3/0 WIRE IS NOT RATED FOR |
| | A 400 AMP SERVICE. PROVIDE CORRECTION. NEC |
| | 310.15(B)(7),(16), FBC RE3603 |
| | |
| | NEW COMMENTS BASED ON SUBMITTED PLANS: |
| | |
| | 4. SHEET E-1 REFERENCED ON COVER SHEET IS NOT INCLUDED |
| | IN PLANS. PROVIDE FULL SET OF PLANS FOR REVIEW. FBC |
| | 107.2.1, 107.3.5 |
| | 5. PROVIDE AFCI PROTECTION AS NOTED: ALL 120-VOLT, |
| | SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS |
| | SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION. NEC 210.12; FBC RE3902.12 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |