2017-09-15 09:00:091ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17060212
 9/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-2: THE 12" TRANSFER DUCT FROM THE MASTER BEDROOM
 IS UNDERSIZED. REFER TO SECTION M1602.4 EXCEPTIONS 1 &
 3, FBC-14 RESIDENTIAL: THE PLAN SHOWS A 10"X16" DUCT
 ENTERING THE MASTER SUITE WHICH, PER THE CODE SECTIONS,
 REQUIRES A TRANSFER DUCT TO SIZED AT 1-1/2 TIMES THE
 CROSS SECTIONAL AREA OF THE 10"X16" DUCT. THE MINIMUM
 TRANSFER DUCT SIZE THEREFORE MUST BE 16".
  
 2) M-2: AS PREVIOUSLY REQUESTED, SHOW THE CONDENSATE
 PIPING RUNS AND DISCHARGE LOCATIONS. SUBMIT SPECS FOR
 THE CONDENSATE PUMPS (IF APPLICABLE)- SECTION M1411.3
  
 3) M-2: AS PREVIOUSLY REQUESTED, PROVIDE INSTALLATION
 DETAILS FOR THE EXTERIOR CONDENSERS- SEE SECTIONS
 M1305.1.4.1 AND M1401.4 .
  
 4) THE PLUMBING PLANS ARE INDICATING A GAS FIREPLACE IN
 THE MASTER BEDROOM AND A NEW GAS RANGE IN THE KITCHEN.
 PLEASE SUBMIT PRODUCT DATA SHEETS FOR BOTH APPLIANCES-
 SECTIONS G2434 & G2435. PLEASE N0OTE COMBUSTION AIR
 SHALL BE REQUIRED IN ACCORDANCE WITH MANUFACTURER'S
 SPECIFICATIONS AND THE SECTION 304 FBC-14 FUEL GAS.
  
 5) PROVIDE A VENTING PLAN FOR THE GAS FIREPLACE WHICH
 SHOWS THE TYPE AND SIZE OF VENT FLUE, THE VENT FLUE
 RUN, AND THE TERMINATION LOCATION- SECTION G2427.
 SUBMIT SPECS FOR THE VENT FLUE.
  
 6) REFER TIO SECTION M1503 AND CLARIFY IF A NEW RANGE
 HOOD WILL BE INSTALLED OVER THE NEW GAS RANGE, AND
 PROVIDE EXHAUST VENTILATION DETAILS AND PRODUCT SPEC
 SHEETS.
  