| 2017-09-19 12:02:49 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P-3 STATES FBC FG TABLE 402.4(2) WAS USED FOR |
| | SIZING THE SYSTEM THAT TABLE IS FOR A .5 LB SYSTEM |
| | UNDER THE GAS SYSTEM INFO IT CALLS OUT A 2LB SYSTEM |
| | PLEASE CLARIFY IF IT IS A .5LB OR 2LB SYSTEM. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT P-2 NOTES A TANKLESS PROPANE WATER HEATER PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT P-1 DETAIL SHOWS A TANK TYPE HEATER SHT P-2+3 |
| | SHOWS A TANKLESS WATER HEATER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. THE MANUAL FOR GAS RANGE DOES NOT LIST BTU LOAD OR |
| | THE STANDARDS THAT IT MEETS SHALL MEET ANSI Z21.1, ANSI |
| | Z21.58 OR ANSI Z83.11 PER FBC FG 623.1 |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. FOR FIRE PLACES AND |
| | RANGE |
| | |
| | 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS SERVING FIRE PLACES PER |
| | FBC-2014 FUEL GAS CODE SEC. 502 THRU 505. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |