| 2017-09-07 13:15:46 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | PREVIOUS COMMENTS NOT ADDRESSED SATISFACTORILY: |
| | |
| | "9. AHU-1 SHOWS A 60 AMP FEED. THE PANEL SCHEDULE |
| | STATES THIS IS A 17.5KW HEAT LOAD, WHICH EQUALS 72.92 |
| | AMPS JUST FOR THE HEAT. PROVIDE CORRECT WIRE AND |
| | BREAKER SIZING. NEC 240.4, 310.15(B)(16), 440.34; FBC |
| | RE3702.11" THE DATA PROVIDED ON SHEET M-2 STATES THAT |
| | AHU-1 WILL HAVE 10KW HEAT AND AHU-2 WILL HAVE 8KW HEAT. |
| | CORRECT DISCREPANCY AND PROVIDE CORRECT WIRE AND |
| | BREAKER SIZES FOR THESE UNITS. NEC 240.4, |
| | 310.15(B)(16), 440.34; FBC RE3702.11 |
| | "10. PROVIDE CARBON MONOXIDE ALARMS AS REQUIRED PER |
| | CODE. FBC RE315.1" CO ALARMS ARE REQUIRED WITHING 10 |
| | FEET OF EACH SLEEPING AREA. SEE REFERENCED CODE AND |
| | PROVIDE CORRECTION. FBC R315.1 |
| | "11. WILL THERE BE A GARAGE DOOR OPENER, WHICH NEEDS AN |
| | OUTLET? CLARIFY AND/OR CORRECT. FBC 107.2.1" GARAGE |
| | DOOR OPENER IS NOW SHOWN, BUT THERE IS NOT A GFCI |
| | PROTECTED OUTLET FOR THE UNIT. PROVIDE CORRECTION. NEC |
| | 210.8; FBC RE3902.2 |
| | "12. PROVIDE DETAIL ON HOW THE FEED FROM TWO 200 AMP |
| | PANELS WILL BE TIED INTO ONE 200 AMP SERVICE. FBC |
| | 107.2.1; NEC 110.3" 400 AMP SERVICE IS SHOWN WITH 3/0 |
| | WIRE FEEDING THE SERVICE. 3/0 WIRE IS NOT RATED FOR A |
| | 400 AMP SERVICE. PROVIDE CORRECTION. NEC |
| | 310.15(B)(7),(16), FBC RE3603 |
| | |
| | NEW COMMENTS BASED ON SUBMITTED PLANS: |
| | |
| | 1. SHEET E-1 REFERENCED ON COVER SHEET IS NOT INCLUDED |
| | IN PLANS. PROVIDE FULL SET OF PLANS FOR REVIEW. FBC |
| | 107.2.1, 107.3.5 |
| | 2. PROVIDE AFCI PROTECTION AS NOTED: ALL 120-VOLT, |
| | SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS |
| | SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION. NEC 210.12; FBC RE3902.12 |
| | 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |