2017-09-07 13:15:46CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PREVIOUS COMMENTS NOT ADDRESSED SATISFACTORILY:
  
 "9. AHU-1 SHOWS A 60 AMP FEED. THE PANEL SCHEDULE
 STATES THIS IS A 17.5KW HEAT LOAD, WHICH EQUALS 72.92
 AMPS JUST FOR THE HEAT. PROVIDE CORRECT WIRE AND
 BREAKER SIZING. NEC 240.4, 310.15(B)(16), 440.34; FBC
 RE3702.11" THE DATA PROVIDED ON SHEET M-2 STATES THAT
 AHU-1 WILL HAVE 10KW HEAT AND AHU-2 WILL HAVE 8KW HEAT.
 CORRECT DISCREPANCY AND PROVIDE CORRECT WIRE AND
 BREAKER SIZES FOR THESE UNITS. NEC 240.4,
 310.15(B)(16), 440.34; FBC RE3702.11
 "10. PROVIDE CARBON MONOXIDE ALARMS AS REQUIRED PER
 CODE. FBC RE315.1" CO ALARMS ARE REQUIRED WITHING 10
 FEET OF EACH SLEEPING AREA. SEE REFERENCED CODE AND
 PROVIDE CORRECTION. FBC R315.1
 "11. WILL THERE BE A GARAGE DOOR OPENER, WHICH NEEDS AN
 OUTLET? CLARIFY AND/OR CORRECT. FBC 107.2.1" GARAGE
 DOOR OPENER IS NOW SHOWN, BUT THERE IS NOT A GFCI
 PROTECTED OUTLET FOR THE UNIT. PROVIDE CORRECTION. NEC
 210.8; FBC RE3902.2
 "12. PROVIDE DETAIL ON HOW THE FEED FROM TWO 200 AMP
 PANELS WILL BE TIED INTO ONE 200 AMP SERVICE. FBC
 107.2.1; NEC 110.3" 400 AMP SERVICE IS SHOWN WITH 3/0
 WIRE FEEDING THE SERVICE. 3/0 WIRE IS NOT RATED FOR A
 400 AMP SERVICE. PROVIDE CORRECTION. NEC
 310.15(B)(7),(16), FBC RE3603
  
 NEW COMMENTS BASED ON SUBMITTED PLANS:
  
 1. SHEET E-1 REFERENCED ON COVER SHEET IS NOT INCLUDED
 IN PLANS. PROVIDE FULL SET OF PLANS FOR REVIEW. FBC
 107.2.1, 107.3.5
 2. PROVIDE AFCI PROTECTION AS NOTED: ALL 120-VOLT,
 SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. NEC 210.12; FBC RE3902.12
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  