| 2017-06-29 10:18:55 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL , ENERGY |
| | CONSERVATION CODES |
| | PERMIT #17060212 |
| | 6/29/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO R101.4.5 ENERGY CONSERVATION: THE |
| | PREVIOUSLY UNCONDITIONED RESIDENCE THAT IS NOW BECOMING |
| | CONDITIONED SPACE SHALL BE BROUGHT INTO FULL COMPLIANCE |
| | WITH THE CODE. PLEASE SEE SECTION R101.5.1 AND SUBMIT |
| | AN ENERGY COMPLIANCE FORM. |
| | |
| | 2) SHEET M-2: THE AC CALC PASTED ON THE PLAN SHEET ARE |
| | NOT CONSISTENT WITH THE AC SYSTEMS SPECIFIED ON THE |
| | PLANS. THE CALCULATION WHICH IS TITLED "SYSTEM #1" ARE |
| | INDICATING A COOLING LOAD OF APPROXIMATELY 25,000 BTUH, |
| | HOWEVER THE PLANS ARE INDICATING SYSTEM 1 AT 60,000 |
| | BTUH AND SYSTEM 2 AT 42,000 BTUH- SEE SECTION R403.6.1 |
| | FBC-14 ENERGY CONSERVATION AND PROVIDE COMPLETE AC |
| | CALCULATIONS INCLUDING THE MANUAL J WORKSHEETS. |
| | |
| | 3) M-2: THE1ST FLOOR MAIN RETURN GRILL SHALL NOT BE |
| | LOCATED IN THE KITCHEN- SECTION M1602 ITEM #4 FBC-14 |
| | RESDIENTIAL. PLEASE RELOCATE THE GRILL AND PROVIDE IT'S |
| | DIMENSIONS. |
| | |
| | 4) M-2: AHU-1 LOCATED IN THE GARAGE SHALL BE PROTECTED |
| | FROM VEHICAL IMPACT- SECTION M1307.3.1 FBC-14 |
| | RESIDENTIAL. |
| | |
| | 5) M-2: PROVIDE THE DIMENSIONS OF THE SECOND FLOOR MAIN |
| | RETURN GRILL IN THE HALLWAY, |
| | |
| | 6) M-2: PROVIDE THE SIZE OF THE TRANSFER DUCT AT THE |
| | 18X10 RETURN FRILL IN THE SECOND FLOOR MASTER BEDROOM. |
| | PLEASE SEE SECTION M1602.4 EXCEPTIONS 1, 2, & 3 TO SIZE |
| | THE RETURN COMPONENTS IN COMPLIANCE WITH THE CODE. |
| | |
| | 7) M-2: SHOW THE CONDENSATE PIPING RUNS AND DISCHARGE |
| | LOCATIONS. SUBMIT SPECS FOR THE CONDENSATE PUMPS (IF |
| | APPLICABLE). |
| | |
| | 8) M-2: THE DRYER EXHAUST DUCT SHALL HAVE A SMOOTH |
| | INTERIOR FINISH AND BE MINIMUM 28 GAUGE- SECTION |
| | M1502.4.1. FLEX DUCTS ARE NOT PERMITTED. |
| | |
| | 9) M-2: PROVIDE INSTALLATION DETAILS FOR THE EXTERIOR |
| | CONDENSERS- SEE SECTIONS M1305.1.4.1 AND M1401.4 . |
| | |