Plan Review Notes
Plan Review Notes For Permit 17060212
Permit Number 17060212
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-22 08:09:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ACCURATE LOAD CALCULATION WITH ALL LOADS
 INCLUDED. CURRENTLY, A/C-2 OR AHU-2 IS NOT INCLUDED.
 NEC 220; FBC RE3602.2
 2. PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONY.
 NEC 210.52(E)(3); FBC RE3901.7
 3. PROVIDE NOTE FOR LIGHTS LOCATED IN TUB/SHOWER AREAS
 TO BE "SUITABLE FOR DAMP LOCATIONS". NEC 410.10(A); FBC
 RE4003.11
 4. PROVIDE CORRECTION FOR BATHROOM GFCI OUTLETS. BATH 1
 AND 2 HAVE RECEPTACLES AND LIGHTING ON THE SAME
 CIRCUIT. CODE STATES: "A MINIMUM OF ONE 20 AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS". NEC 210.11(C)(3); FBC RE3703.4
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 6. PLAN APPEARS TO SHOW AN OUTLET IN THE SHOWER AREA OF
 BATH 1. PROVIDE CORRECTION AND/OR CLARIFICATION. FBC
 107.2.1; NEC 406.9(C); FBC RE4002.11
 7. PANEL A, CIRCUIT 17 IS LABELED AS A 15 AMP CIRCUIT.
 CODE REQUIRES A 20 AMP CIRCUIT. LIGHTING NOT PERMITTED
 ON SAME CIRCUIT. PROVIDE CORRECTION. NEC 210.11(C),
 210.52(B); FBC RE3901.3
 8. AHU-2 SHOWS A CIRCUIT THAT IS #6 WIRE ON A 60 AMP
 BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE CORRECTION.
 NEC 334.80; FBC RE3705.4.4
 9. AHU-1 SHOWS A 60 AMP FEED. THE PANEL SCHEDULE STATES
 THIS IS A 17.5KW HEAT LOAD, WHICH EQUALS 72.92 AMPS
 JUST FOR THE HEAT. PROVIDE CORRECT WIRE AND BREAKER
 SIZING. NEC 240.4, 310.15(B)(16), 440.34; FBC RE3702.11
 10. PROVIDE CARBON MONOXIDE ALARMS AS REQUIRED PER
 CODE. FBC R315.1
 11. WILL THERE BE A GARAGE DOOR OPENER, WHICH NEEDS AN
 OUTLET? CLARIFY AND/OR CORRECT. FBC 107.2.1
 12. PROVIDE DETAIL ON HOW THE FEED FROM TWO 200 AMP
 PANELS WILL BE TIED INTO ONE 200 AMP SERVICE. FBC
 107.2.1; NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  