| 2017-08-08 10:58:32 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | NO MECHANICAL INFORMATION WAS SUBMITTED FOR THE FIRST |
| | REVIEW. THIS IS THE FIRST TIME MECHANICAL INFORMATION |
| | IS SUBMITTED. |
| | |
| | 1- A/C DRAWING SUBMITTED HAS A COPY OF THE ARCHITECT'S |
| | SEAL AND SIGNATURE. A/C PLANS NEEDS TO HAVE THE |
| | ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT SHOWN ON |
| | THE TITLE BLOCK AS REQUIRED BY CHAPTER 481 F.S. WHEN |
| | SUBMITTING DRAWINGS FOR PUBLIC RECORDS. |
| | |
| | 2- THE LEISURE ROOM NEEDS TO COMPLY WITH THE BALANCED |
| | RETURN AIR SECTION M1602.4 FBC-RESIDENTIAL. 5TH EDITION |
| | (2014). REVISE A/C PLAN AS REQUIRED. |
| | |
| | 3- IT LOOKS LIKE THE RETURN AIR GRILL SHOWN ON THE |
| | LIVING ROOM IS TOO CLOSE TO THE EXISTING FIREPLACE. IT |
| | LOOKS LIKE IT'S LESS THAN 10 FEET. THIS IS A PROHIBITED |
| | LOCATION. REVISE AS REQUIRED. SEC. M1602.2 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- EQUIPMENT SIZING CALCULATIONS SUBMITTED: |
| | A) PLAN FOR A/C SUBMITTED SHOWS THAT AIR IS DISTRIBUTED |
| | TO ALL ROOMS, INCLUDING THE LEISURE ROOM. CALCULATIONS |
| | SUBMITTED DON'T INCLUDE THIS ROOM. REVISE AS REQUIRED |
| | TO MATCH PLAN. SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | B) CFM'S SHOWN ON THE CALCULATIONS DON'T MATCH CFM |
| | SHOWN ON A/C PLAN. REVISE AS REQUIRED TO MATCH. SEC. |
| | R403.6.1 FBC-ENERGY CONSERVATION. |
| | |
| | C) SIZE OF ROOMS AND AREA OF ROOMS DON'T MATCH PLANS. |
| | REVISE AS REQUIRE TO MATCH. SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) COORDINATE ALL THE COMPONENTS OF THE HOUSE WITH |
| | PLANS. NOT ALL THE WALLS ARE CONCRETE BLOCK WALL. THERE |
| | ARE SOME WOOD FRAMED WALLS. ALSO, USE THE SOFTWARE |
| | DEFAULT FACTOR FOR GLAZING U-FACTOR AND SHGC FACTOR OR |
| | PROVIDE INFORMATION SHOWING THAT THE EXISTING WINDOWS |
| | HAVE THE SPECIFIED FACTORS. REVISE AS REQUIRED TO MATCH |
| | PLANS. SEC. R403.6.1 FBC-ENERGY CONSERVATION. |
| | |
| | E) PAGE OF 12 OF CALCULATIONS SUBMITTED SPECIFY NATURAL |
| | GAS FURNACE AS THE HEATING SYSTEM. PLANS DON'T SHOW ANY |
| | NATURAL GAS FURNACE. REVISE AS REQUIRED TO MATCH PLANS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD |
| | DRAWINGS FOR REVIEW. |
| | |