| Date |
Text |
| 2017-08-07 11:46:10 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND |
| | DATE AT THE BOTTOM OF THE FORM AS REQUIRED SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 IS |
| | INCORRECT. THE NEW A/C AREA IS THE MASTER SUITE AND |
| | LEISURE ROOM. SEE A/C PLAN. REVISE AS REQUIRED TO MATCH |
| | PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D) WALL TYPES INFORMATION ON ITEM #9 IS MISSING THE |
| | INFORMATION FOR THE LEISURE ROOM. THIS IS NOT CONCRETE |
| | BLOCK. ALSO, NEED TO ADD THE FRAMED WALL AREA AT |
| | EXISTING GARAGE DOOR OPENING TO BE CLOSED. SEE PLANS |
| | FOR SPECIFIED INSULATION R-VALUE. REVISE AS REQUIRED. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E) CEILING AREA ON ITEM #10 NEEDS TO BE COORDINATED |
| | WITH CORRECT A/C AREA ON ITEM # 1(C) ABOVE. REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F) ROOF TYPE SPECIFIED ON PAGE 2 OF 4 IS INCORRECT. |
| | MISSING THE GABLE END AREA. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) CEILING R-VALUE SPECIFIED ON PAGE 2 OF 4 DOESN'T |
| | MATCH INFORMATION SPECIFIED ON ITEM #10 ON PAGE 1 OF 4 |
| | AND PLANS. REVISE AS REQUIRED TO MATCH. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4 TO MATCH |
| | PLANS. REVISE WINDOW ORIENTATION AND SQUARE FOOTAGE TO |
| | MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS IS |
| | REQUIRED WHEN THE CALCULATIONS ARE NOT DONE USING THE |
| | DEFAULT FACTOR FOR GLAZING. |
| | |
| | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. |
| | |
| | 3- NEW MASTER BEDROOM: CLEARLY SPECIFY TYPE AND SIZE OF |
| | EGRESS WINDOW. AND, PROVIDE MANUFACTURER'S CUT SHEETS |
| | FOR THE SPECIFIED SIZE (24EH) TO VERIFY COMPLIANCE WITH |
| | THE EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. |
| | ALSO, REVISE THE WINDOW EGRESS NOTE SHOWN ON SHEET A-2 |
| | BELOW THE PROPOSED FLOOR PLAN. THE CODE TO BE |
| | REFERENCED FOR SINGLE FAMILY RESIDENCES IS THE |
| | RESIDENTIAL CODE NOT THE BUILDING CODE. THE CORRECT |
| | SEC. IS R310. ALSO, IS MISSING THE MINIMUM HEIGHT |
| | DIMENSION. REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. NO |
| | INFORMATION WAS SUBMITTED TO VERIFY EGRESS WINDOW |
| | COMPLIANCE. |
| | |
| | 4- NEW MASTER BEDROOM: PROVIDE SPECIFICATIONS FOR THE |
| | INSULATION IN WALLS. NOTE: COORDINATE WITH THE ENERGY |
| | CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. |
| | RESPONSE: CONCRETE BLOCK WALL INSULATION R-VALUE IS NOT |
| | SPECIFIED. COORDINATE WITH THE ENERGY CALCULATIONS. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) NEW SWING DOOR AS SPECIFIED ON PLANS FOR THE NEW |
| | LEISURE ROOM. |
| | RESPONSE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | THAT CORRESPONDS TO DRAWINGS SUBMITTED. IF THERE IS NOT |
| | FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA, THEN |
| | MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. |
| | COMPLETE ORIGINAL ENGINEERED PACKAGE WILL BE REQUIRED. |
| | |
| | B) THE WINDOWS IN THE NEW LEISURE ROOM NEED TO HAVE |
| | HURRICANE IMPACT PROTECTION AS REQUIRED BY SEC. |
| | R301.2.1.2 FBC-RESIDENTIAL. SHOW COMPLIANCE. IF THE |
| | WINDOWS ARE NON-IMPACT, THEN SHUTTERS ARE REQUIRED. IF |
| | SHUTTERS ARE REQUIRED, THEN, PROVIDE SHUTTERS PRODUCT |
| | APPROVALS AND COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | |
| | 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ( NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: PLEASE PLACE REVIEW STAMP ON THE COVER OF THE |
| | PRODUCT APPROVAL NOT ON THE BACK OF THE FRONT PAGE. |
| | STAMPS ON THE BACK OF THE FRONT PAGE ARE NOT PRACTICAL |
| | FOR THE CITY RECORDS RETENTION PROCEDURE. |
| | |
| | 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR THE NEW LEISURE ROOM EXTERIOR DOOR. SPECIFY ALL |
| | FRAMING MEMBERS AND CONNECTORS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: PROVIDE COMPLETE FRAMING DETAIL. SPECIFY ALL |
| | FRAMING MEMBERS AND CONNECTORS. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL THE LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. REVISE VALUATION AS REQUIRED AND INCLUDE |
| | THE DESIGN PROFESSIONAL FEES. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 9- PROVIDE COPIES OF TESTING DONE FOR 3M SAFETY FILM. |
| | WINDOWS IN THE LEISURE ROOM BY THE NEW WASHER/DRYER |
| | NEED TO HAVE SAFETY GLASS AS REQUIRED BY SEC. R308.4.2 |
| | FBC-RESIDENTIAL. SHOW COMPLIANCE WITH THIS REQUIREMENT. |
| | NOTE: PROVIDE COPIES OF TESTING DONE FOR THE 3M SAFETY |
| | FILM AS REQUIRED BY SEC. R308.3.1 FBC-RESIDENTIAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD |
| | DRAWINGS FOR REVIEW. |
| | |