Plan Review Notes
Plan Review Notes For Permit 17060195
Permit Number 17060195
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-24 15:03:101) SHOW THE SPACING BETWEEN THE FUEL TANKS. COMPLY WITH
 NFPA 30, SEC. 15.3 & TABLE 15.3.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) LABEL ALL DROP PIPES ENTERING THE TANKS.( THERE IS A
 DROP PIPE IN THE GASOLINE TANK THAT IS LOCATED BETWEEN
 THE DISPENSER AND FUEL FILL PORT AND ALSO IN THE DIESEL
 TANK LOCATED IN THE LEFT SIDE OF THE TANK NEXT TO THE
 CLOCK GAUGE THAT IS NOT IDENTIFIED.)WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) SHOW THE SIZE OF ALL VENTS & THE WITHDRAWL
 CONNECTIONS / DROP TUBES ON EACH TANK. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR BOTH
 TANKS.WPB AMEND. TO FBC SEC. 107.2.1.
 5) INDICATE THE TYPE OF PIPE MATERIAL USED FOR THE TANK
 VENTS. MATERIALS SHALL COMPLY WITH NFPA 30 SEC. 27.4.1
 & ASME B31.
 6) EACH CONNECTION TO AN ABOVE GROUND TANK THROUGH
 WHICH LIQUID CAN NORMALLY FLOW SHALL BE PROVIDED WITH
 AN INTERNAL OR AN EXTERNAL VALVE LOCATED AS CLOSE AS
 PRACTICAL TO THE SHELL OF THE TANK PER NFPA 30
 SEC.22.13.2. ( REFER TO DISPENSER LINES.
 7) INSTALLATION INSTRUCTIONS FOR ABOVE GROUND STORAGE
 TANKS. - FACTORY-BUILT ABOVEGROUND TANKS SHALL BE
 PROVIDED WITH INSTRUCTIONS FOR TESTING THE TANKS AND
 FOR INSTALLATION OF THE NORMAL AND EMERGENCY VENTS.
 NFPA 30 SEC. 22.16.
 8) SUBMIT A KEY PLAN AND SITE PLAN SHOWING THE LOCATION
 OF THE FUEL TANKS AND THE DISTANCES FROM ANY ADJOINING
 BUILDINGS. WPB AMEND. TO FBC SEC. 107.2.1.
 9) IF THESE TANKS WILL BE EXPOSED TO ANY TYPE OF
 VEHICULAR TRAFFIC THEN COLLISION PROTECTION SHALL BE
 PROVIDED PER NFPA 30 SEC.22.15. CLARIFY.
 10) STATIC ELECTRICITY. - MEANS SHALL BE PROVIDED TO
 MINIMIZE GENERATION OF STATIC ELECTRICITY PER NFPA 30
 SEC. 18.5.2.2. SUCH MEANS SHALL MEET THE REQUIREMENTS
 OF NFPA 30 SEC.6.5.4.
 11) SUBMIT MANUF. SPECIFICATIONS FOR THE HOSES,
 DISPENSERS, VALVES, ETC. PIPING, VALVES AND FITTINGS
 SHALL COMPLY WITH NFPA 30 CHAPTER 27.
 12) WHERE PUMPS ARE USED FOR LIQUID TRANSFER, MEANS
 SHALL BE PROVIDED TO DEACTIVATE LIQUID TRANSFER IN THE
 EVENT OF A LIQUID SPILL OR FIRE PER NFPA 30 SEC.
 18.5.2.3.
 13) IF HOSE IS USED IN THE TRANSFER OPERATION, IT SHALL
 BE EQUIPPED WITH A SELF-CLOSING VALVE WITHOUT A
 HOLD-OPEN LATCH IN ADDITION TO THE OUTLET VALVE. ONLY
 LISTED OR APPROVED HOSE SHALL
 BE USED. NFPA 30 SEC. 18.5.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW