2017-07-27 11:04:595444 NORTH HAVERHILL ROAD - FUEL STORAGE AND DISPENSING
 TRACKING: 17060195
 PERMIT: 17021052
  
 DESIGN AND INSTALLATION SHALL CONFORM TO NFPA 1 - FIRE
 CODE: CHAPTER 42 - FUEL STORAGE AND REFUELING
  
 NFPA 1 - SECTION 42.5.2.3 FUEL DISPENSING SYSTEMS,
 INCLUDING DISPENSERS, HOSES, NOZZLES, BREAKAWAY
 FITTINGS, SWIVELS, FLEXIBLE CONNECTORS, DISPENSER
 EMERGENCY SHUTOFF VALVES, VAPOR RECOVERY SYSTEMS, AND
 PUMPS THAT ARE USED FOR ALCOHOL-BLENDED MOTOR FUELS
 SHALL BE LISTED OR APPROVED FOR THE SPECIFIC PURPOSE.
  
 NFPA 1 - SECTION 42.7.5.2 OPERATING INSTRUCTIONS SHALL
 BE CONSPICUOUSLY POSTED IN THE DISPENSING AREA. THE
 INSTRUCTIONS SHALL INCLUDE LOCATION OF EMERGENCY
 CONTROLS AND A REQUIREMENT THAT THE USER STAY OUTSIDE
 OF HIS/HER VEHICLE AND IN VIEW OF THE FUELING NOZZLE
 DURING DISPENSING. [30A:9.5.2]
  
 NFPA 1 SECTION 42.7.5.3 ADDITIONAL EMERGENCY
 INSTRUCTIONS SHALL BE CONSPICUOUSLY POSTED IN THE
 DISPENSER AREA. THE INSTRUCTIONS SHALL INCORPORATE THE
 FOLLOWING OR EQUIVALENT WORDING:
 EMERGENCY INSTRUCTIONS: IN CASE OF FIRE OR SPILL
 (1) USE EMERGENCY STOP BUTTON.
 (2) REPORT ACCIDENT BY CALLING (SPECIFY LOCAL FIRE
 NUMBER).REPORT LOCATION.
  
 NFPA 1 SECTION 42.7.2.5.4 SIGNS. WARNING SIGNS SHALL BE
 CONSPICUOUSLY POSTED IN THE DISPENSING AREA AND SHALL
 INCORPORATE THE FOLLOWING OR EQUIVALENT WORDING:
 WARNING:
 IT IS UNLAWFUL AND DANGEROUS TO DISPENSE GASOLINE INTO
 UNAPPROVED CONTAINERS.
 NO SMOKING.
 STOP MOTOR.
 NO FILLING OF PORTABLE CONTAINERS IN OR ON A MOTOR
 VEHICLE.
 PLACE CONTAINER ON GROUND BEFORE FILLING.
 DISCHARGE YOUR STATIC ELECTRICITY BEFORE FUELING BY
 TOUCHING A METAL SURFACE AWAY FROM THE NOZZLE.
 DO NOT RE-ENTER YOUR VEHICLE WHILE GASOLINE IS PUMPING.
 IF A FIRE STARTS, DO NOT REMOVE NOZZLE ? BACK AWAY
 IMMEDIATELY.
 DO NOT ALLOW INDIVIDUALS UNDER LICENSED AGE TO USE THE
 PUMP
  
 NFPA 1 SECTION 42.7.2.3.1 CLASS I OR CLASS II LIQUIDS
 SHALL NOT BE DISPENSED INTO PORTABLE CONTAINERS UNLESS
 THE CONTAINER IS CONSTRUCTED OF METAL OR IS APPROVED BY
 THE AHJ, HAS A TIGHT CLOSURE, AND IS FITTED WITH A
 SPOUT OR SO DESIGNED THAT THE CONTENTS CAN BE POURED
 WITHOUT SPILLING. THE HOSE NOZZLE VALVE SHALL BE
 MANUALLY HELD OPEN DURING THE DISPENSING OPERATION.
  
 NO PRODUCT DATA SUBMITTED FOR THE FUEL TANKS, PUMP,
 DISPENSER, STAIRS OR WORK PLATFORM.
  
 NO INFORMATION PROVIDED HOW THE STORAGE TANKS AND
 REFUELING VEHICLE WILL BE BONDED AND GROUNDED.
  
 HOW WILL THE STORAGE TANKS BE PROTECTED FROM VEHICULAR
 DAMAGE? IT APPEARS THE MOWERS, CARTS AND ATVS WOULD BE
 ENTERING INTO THE ROOFED STRUCTURE TO BE REFUELED.
  
 NO PORTABLE FIRE EXTINGUISHERS PROVIDED TO PROTECT THE
 HAZARD. NFPA 1 - SECTION 42.7.2.5. 2 EXTINGUISHERS FOR
 OUTSIDE MOTOR FUEL DISPENSING AREAS SHALL BE PROVIDED
 ACCORDING TO THE EXTRA (HIGH) HAZARD REQUIREMENTS FOR
 CLASS B HAZARDS, EXCEPT THAT THE MAXIMUM TRAVEL
 DISTANCE TO AN 80 B:C EXTINGUISHER SHALL BE PERMITTED
 TO BE 100 FEET.
  
 PROVIDE NO SMOKING OR OPEN FLAME WEATHERPROOF SIGNAGE.
  
 PROVIDE NFPA 704 DIAMOND PLACARD INDICATING THE HAZARDS
 OF THE FUELS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WPB FIRE RESCUE