| 2017-07-27 11:04:59 | 5444 NORTH HAVERHILL ROAD - FUEL STORAGE AND DISPENSING |
| | TRACKING: 17060195 |
| | PERMIT: 17021052 |
| | |
| | DESIGN AND INSTALLATION SHALL CONFORM TO NFPA 1 - FIRE |
| | CODE: CHAPTER 42 - FUEL STORAGE AND REFUELING |
| | |
| | NFPA 1 - SECTION 42.5.2.3 FUEL DISPENSING SYSTEMS, |
| | INCLUDING DISPENSERS, HOSES, NOZZLES, BREAKAWAY |
| | FITTINGS, SWIVELS, FLEXIBLE CONNECTORS, DISPENSER |
| | EMERGENCY SHUTOFF VALVES, VAPOR RECOVERY SYSTEMS, AND |
| | PUMPS THAT ARE USED FOR ALCOHOL-BLENDED MOTOR FUELS |
| | SHALL BE LISTED OR APPROVED FOR THE SPECIFIC PURPOSE. |
| | |
| | NFPA 1 - SECTION 42.7.5.2 OPERATING INSTRUCTIONS SHALL |
| | BE CONSPICUOUSLY POSTED IN THE DISPENSING AREA. THE |
| | INSTRUCTIONS SHALL INCLUDE LOCATION OF EMERGENCY |
| | CONTROLS AND A REQUIREMENT THAT THE USER STAY OUTSIDE |
| | OF HIS/HER VEHICLE AND IN VIEW OF THE FUELING NOZZLE |
| | DURING DISPENSING. [30A:9.5.2] |
| | |
| | NFPA 1 SECTION 42.7.5.3 ADDITIONAL EMERGENCY |
| | INSTRUCTIONS SHALL BE CONSPICUOUSLY POSTED IN THE |
| | DISPENSER AREA. THE INSTRUCTIONS SHALL INCORPORATE THE |
| | FOLLOWING OR EQUIVALENT WORDING: |
| | EMERGENCY INSTRUCTIONS: IN CASE OF FIRE OR SPILL |
| | (1) USE EMERGENCY STOP BUTTON. |
| | (2) REPORT ACCIDENT BY CALLING (SPECIFY LOCAL FIRE |
| | NUMBER).REPORT LOCATION. |
| | |
| | NFPA 1 SECTION 42.7.2.5.4 SIGNS. WARNING SIGNS SHALL BE |
| | CONSPICUOUSLY POSTED IN THE DISPENSING AREA AND SHALL |
| | INCORPORATE THE FOLLOWING OR EQUIVALENT WORDING: |
| | WARNING: |
| | IT IS UNLAWFUL AND DANGEROUS TO DISPENSE GASOLINE INTO |
| | UNAPPROVED CONTAINERS. |
| | NO SMOKING. |
| | STOP MOTOR. |
| | NO FILLING OF PORTABLE CONTAINERS IN OR ON A MOTOR |
| | VEHICLE. |
| | PLACE CONTAINER ON GROUND BEFORE FILLING. |
| | DISCHARGE YOUR STATIC ELECTRICITY BEFORE FUELING BY |
| | TOUCHING A METAL SURFACE AWAY FROM THE NOZZLE. |
| | DO NOT RE-ENTER YOUR VEHICLE WHILE GASOLINE IS PUMPING. |
| | IF A FIRE STARTS, DO NOT REMOVE NOZZLE ? BACK AWAY |
| | IMMEDIATELY. |
| | DO NOT ALLOW INDIVIDUALS UNDER LICENSED AGE TO USE THE |
| | PUMP |
| | |
| | NFPA 1 SECTION 42.7.2.3.1 CLASS I OR CLASS II LIQUIDS |
| | SHALL NOT BE DISPENSED INTO PORTABLE CONTAINERS UNLESS |
| | THE CONTAINER IS CONSTRUCTED OF METAL OR IS APPROVED BY |
| | THE AHJ, HAS A TIGHT CLOSURE, AND IS FITTED WITH A |
| | SPOUT OR SO DESIGNED THAT THE CONTENTS CAN BE POURED |
| | WITHOUT SPILLING. THE HOSE NOZZLE VALVE SHALL BE |
| | MANUALLY HELD OPEN DURING THE DISPENSING OPERATION. |
| | |
| | NO PRODUCT DATA SUBMITTED FOR THE FUEL TANKS, PUMP, |
| | DISPENSER, STAIRS OR WORK PLATFORM. |
| | |
| | NO INFORMATION PROVIDED HOW THE STORAGE TANKS AND |
| | REFUELING VEHICLE WILL BE BONDED AND GROUNDED. |
| | |
| | HOW WILL THE STORAGE TANKS BE PROTECTED FROM VEHICULAR |
| | DAMAGE? IT APPEARS THE MOWERS, CARTS AND ATVS WOULD BE |
| | ENTERING INTO THE ROOFED STRUCTURE TO BE REFUELED. |
| | |
| | NO PORTABLE FIRE EXTINGUISHERS PROVIDED TO PROTECT THE |
| | HAZARD. NFPA 1 - SECTION 42.7.2.5. 2 EXTINGUISHERS FOR |
| | OUTSIDE MOTOR FUEL DISPENSING AREAS SHALL BE PROVIDED |
| | ACCORDING TO THE EXTRA (HIGH) HAZARD REQUIREMENTS FOR |
| | CLASS B HAZARDS, EXCEPT THAT THE MAXIMUM TRAVEL |
| | DISTANCE TO AN 80 B:C EXTINGUISHER SHALL BE PERMITTED |
| | TO BE 100 FEET. |
| | |
| | PROVIDE NO SMOKING OR OPEN FLAME WEATHERPROOF SIGNAGE. |
| | |
| | PROVIDE NFPA 704 DIAMOND PLACARD INDICATING THE HAZARDS |
| | OF THE FUELS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WPB FIRE RESCUE |
| | [email protected] |