| Plan Review Notes For Permit 17060195 |
| Permit Number |
17060195 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 10:19:42 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | NEED TO IDENTIFY THE CLASS LOCATION IN AND AROUND THE | | | TANKS AND PUMP. | | | | | | 500.4 GENERAL | | | (A) DOCUMENTATION. A LL AREAS DESIGNATED AS HAZARDOUS | | | (CLASSIFIED) | | | LOCATIONS SHALL BE PROPERLY DOCUMENTED. THIS | | | DOCUMENTATION | | | SHALL BE AVAILABLE TO THOSE AUTHORIZED TO DESIGN, | | | INSTALL, INSPECT, | | | MAINTAIN, OR OPERATE ELECTRICAL EQUIPMENT AT THE | | | LOCATION. | | | | | | NEED TO SHOW DISCONNECT, WIRE SIZES AND SEAL OFFS USED | | | IN THIS INSTALLATION. | | | NEED TO SHOW WHERE THESE ARE FED FROM CIRCUIT NUMBER | | | AND LOCATION, |
|