2017-08-05 08:23:512014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17060195
 W. P. B. PERMIT: 17021052
 ADD: 5444 N HAVERHILL RD. FUEL TANK AT STADIUM
 MAINTENANCE SHOP
 CONT: CYPRESS CONSTRUCTION GROUP
 TEL: 954-533-1199
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. / SAT. AUGUST 5/ 2017
 ACTION: DENIED
  
 1A) ON THE ORIGINAL PERMIT NUMBER 17021052 THERE WAS NO
 BUILDING REVIEW. ON THE ORIGINAL PLANS FOR THIS
 STRUCTURES THEY WERE A ROOFED OVER OPEN STRUCTURE UNDER
 THE PRIME PERMIT 16020418 SEE SHEET 0602-62.612. UNDER
 THE PERMIT 17021052 THE PLANS SHOW WHAT CANNOT BE
 DEFINED, SINCE THE REMAINDER OF THE BUILDING IS NOT
 INCLUDED. THE AREA SHOWN WITH THE (2) 500 GALLON TANKS
 CANNOT BE DETERMINED IF THIS IN THE LAST BAY OF THE
 BUILDING OR THE OPEN WALLED IN AREA NEXT TO THE
 BUILDING?
  
 1B) THE PLANS SHOWS THE FRONT ENCLOSED AND DOORS OR
 GATES INSTALLED. THIS IS BEYOND THE SCOPE OF A PCC
 LICENSE; A CGC CAN ENCLOSE THE STRUCTURE. FLORIDA
 STATUTE 489.105(A).
  
 2) PLANS ARE SILENT AS TO THE BUILDING CLASSIFICATION
 AND IF FIRE SPRINKLERED OR NOT AND OCCUPANCY TYPE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE SPRINKLERED OR NOT?
 FIRE RATING OF WALLS AND DOORS
  
 3) FUEL TANK WIND LOAD CALCULATIONS WERE SUBMITTED
 PLEASE PROVIDE ADDITIONAL INFORMATION EVEN IN THIS
 REVISION SHEET 0927-1 P$-003 SHOWS (2) 500 GALLON TANKS
 WITHIN THE BUILDING? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) THE SUBMITTED WIND CALCULATIONS SHEET 3 OF 9 SHOWS
 WHAT APPEARS TO BE A COPY OF A SCANNED PAPER
 SIGNED AND SEALED DOCUMENT. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 5) PLEASE SUBMIT MSDS SHEETS FOR BOTH THE GASOLINE AND
 DIESEL FUELS TO CONFIRM THE CLASS OF COMBUSTIBILITY,
 AND REQUIREMENTS. FOR THIS REVIEW WE WILL USE THE
 FOLLOWING ASSUMPTIONS;
 GASOLINE FUEL TO BE A CLASS 1A FLAMMABLE LIQUID, ALL
 GRADES OF FUEL.
 DIESEL FUEL TO BE A CLASS 3 FLAMMABLE LIQUID. (USING
 DIESEL GRADE # 2).
 PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 414.1.3
 INFORMATION REQUIRED. A REPORT SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL IDENTIFYING THE MAXIMUM EXPECTED
 QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED, USED IN
 A CLOSED SYSTEM AND USED IN AN OPEN SYSTEM, AND
 SUBDIVIDED TO SEPARATELY ADDRESS HAZARDOUS MATERIAL
 CLASSIFICATION CATEGORIES BASED ON TABLES 307.1(1) AND
 307.1(2). THE METHODS OF PROTECTION FROM SUCH HAZARDS,
 INCLUDING BUT NOT LIMITED TO CONTROL AREAS, FIRE
 PROTECTION SYSTEMS AND GROUP H OCCUPANCIES SHALL BE
 INDICATED IN THE REPORT AND ON THE CONSTRUCTION
 DOCUMENTS. THE OPINION AND REPORT SHALL BE PREPARED BY
 A QUALIFIED PERSON, FIRM OR CORPORATION APPROVED BY THE
 BUILDING OFFICIAL AND PROVIDED WITHOUT CHARGE TO THE
 ENFORCING AGENCY.
  
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
  
 6) DEPENDING ON THE AMOUNT OF FLAMMABLE LIQUIDS BEING
 STORED, IF INDOORS OR OUTSIDE SHOW COMPLIANCE WITH;
 2014 FBC 414.2 CONTROL AREAS.
 CONTROL AREAS SHALL COMPLY WITH SECTIONS 414.2.1
 THROUGH 414.2.5 AND THE FLORIDA FIRE PREVENTION CODE.
  
 [F] 414.2.1 CONSTRUCTION REQUIREMENTS. CONTROL AREAS
 SHALL BE SEPARATED FROM EACH OTHER BY FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
  
 [F] 414.2.2 PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITIES.
 THE PERCENTAGE OF MAXIMUM ALLOWABLE QUANTITIES OF
 HAZARDOUS MATERIALS PER CONTROL AREA PERMITTED AT EACH
 FLOOR LEVEL WITHIN A BUILDING SHALL BE IN ACCORDANCE
 WITH TABLE 414.2.2.
  
 7) SHEET 0927-1 P4-003 SHOWS WHAT APPEARS TO BE A
 DOUBLE WALL TANK AND LEAK DETECTOR PLEASE PROVIDE THE
 MANUFACTURERS CUT SHEETS FOR THIS TANK SYSTEM IN
 ACCORDANCE WITH FBC-B 414.5.4.
  
 8) DEPICTED ON SHEET 0927-1 P4-003 IT APPEARS THE PUMP
 AND DISPENSER WITH HOSE IS ON TOP OF THE 500 GALLON
 TANK. BOTH TANKS ARE WELL WITHIN THE STRUCTURE, PLEASE
 PROVIDE HOW COMPLIANCE WITH DISPENSING OF FUEL WILL
 OCCUR AND IN COMPLIANCE WITH FBC-B 414.7.2 414.7.2
 DISPENSING, USE AND HANDLING. WHERE IS THE EMERGENCY
 SHUT OFF LOCATED?
  
 9) DEPICTED ON SHEET 0927-1 P4-003 IS NOTE # 3,
 PETROVEND FUEL SYSTEM CONTROL PANEL AND CARD READER
 PLEASE PROVIDE COMPLIANCE WITH 414.7.3 SUPERVISION AND
 MONITORING.
  
 10A) IF THE DISPENSING SYSTEMS ARE INSIDE THEY WILL
 NEED TO COMPLY WITH 414.5 INSIDE STORAGE, DISPENSING
 AND USE. THE INSIDE STORAGE, DISPENSING AND USE OF
 HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH
 SECTIONS 414.5.1 THROUGH 414.5.4 OF THIS CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 10B) IF THE DISPENSING SYSTEMS ARE OUTSIDE THEY WILL
 NEED TO COMPLY WITH 414.6 OUTDOOR STORAGE, DISPENSING
 AND USE. THE OUTDOOR STORAGE, DISPENSING AND USE OF
 HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved