2017-06-30 12:37:041ST REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION
 CODES
 PERMIT #17060192
 6/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE NOTE AT RTU #1 TO SET THE O/A INTAKE
 TO 140 CFMS IS INCORRECT AND IN CONFLICT WITH THE
 VENTILATION CALCULATION TABLE WHICH IS SPECIFYING 426
 CFMS FOR THE RECREATION RM. PLEASE INCLUDE THE LOBBY IN
 THE CALCULATIONS.
  
 2) M-1: THE VENTILATION CALCULATION FOR THE GYM IS NOT
 IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES 0.30 CFMS
 PER SF FOR A GYM, HOWEVER THE CLASSIFICAIONS FOR THIS
 SPACE MAY BE CLOSER TO HEALTH CLUB/AEROBICS ROOMS WITH
 REQUIRES AN OCCUPANT DENSITY CALCULATION OF 40 PERSONS
 PER SF. OR 22 PERSONS LOAD IN THE 550 SF. THE CALC
 WOULD THEN RESULT TO 22 PERSONS X 20 CFMS= 440 CFMS +
 ,06 X550= 33 CFMS FOR A TOTAL OF 473 CFMS FOR THE
 SPACE. PLEASE CORRECT ACCORDINGLY.
  
 3) M-1: CLARIFY IF THE AC CLOSETS ARE BOTH OPEN PLENUM
 CLOSETS AS SHOWN IN THE DETAIL ON M2, AND INDICATE WHAT
 TYPE OF DOOR WILL ENCLOSE THE AHU #3 CLOSET- IT IS NOT
 SHOWN ON THE ARCHITECTURAL PLANS. DOOR #5 WHICH
 ENCLOSES THE AHU #2 CLOSET IS A WOOD DOOR WHICH IS
 COMPLIANT IF THE RETURN IS DUCTED DIRECTLY TO THE AHU.
 OTHERWISE A NON-COMBUSTIBLE DOOR IS REQUIRED PER
 SECTIONS
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND
 SECTION 602 FBC-14 MECHANICAL.
  
 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR THE
 RTU AND CONDENSER INSTALLATIONS- SEE SECTION 301.15
 FBC-14 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 5) M-2: CORRECT NOTE #3 AT THE AHU MOUNTING DETAIL
 WHICH IS REFERENCING A RESIDIENTIAL CODE SECTION, AND
 SEE SECTION C403.2.7.3.3 WHICIH REQUIRES A MINIMUM 4"
 CLEARANCE SPACE AROUND THE AIR HANDLER.
  
 6) ENERGYGAUGE COMPLIANCE SUBMITTAL: A) THE
 OWNER/AGENT'S SIGNATURE IS MISSING- PAGE 3. B) THE
 DESIGNER OR ENGINEER'S MANDATORY REQUIREMENTS CHECKLIST
 NOT COMPLETED- PAGE 8.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  