| 2017-06-30 12:37:04 | 1ST REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17060192 |
| | 6/30/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: THE NOTE AT RTU #1 TO SET THE O/A INTAKE |
| | TO 140 CFMS IS INCORRECT AND IN CONFLICT WITH THE |
| | VENTILATION CALCULATION TABLE WHICH IS SPECIFYING 426 |
| | CFMS FOR THE RECREATION RM. PLEASE INCLUDE THE LOBBY IN |
| | THE CALCULATIONS. |
| | |
| | 2) M-1: THE VENTILATION CALCULATION FOR THE GYM IS NOT |
| | IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES 0.30 CFMS |
| | PER SF FOR A GYM, HOWEVER THE CLASSIFICAIONS FOR THIS |
| | SPACE MAY BE CLOSER TO HEALTH CLUB/AEROBICS ROOMS WITH |
| | REQUIRES AN OCCUPANT DENSITY CALCULATION OF 40 PERSONS |
| | PER SF. OR 22 PERSONS LOAD IN THE 550 SF. THE CALC |
| | WOULD THEN RESULT TO 22 PERSONS X 20 CFMS= 440 CFMS + |
| | ,06 X550= 33 CFMS FOR A TOTAL OF 473 CFMS FOR THE |
| | SPACE. PLEASE CORRECT ACCORDINGLY. |
| | |
| | 3) M-1: CLARIFY IF THE AC CLOSETS ARE BOTH OPEN PLENUM |
| | CLOSETS AS SHOWN IN THE DETAIL ON M2, AND INDICATE WHAT |
| | TYPE OF DOOR WILL ENCLOSE THE AHU #3 CLOSET- IT IS NOT |
| | SHOWN ON THE ARCHITECTURAL PLANS. DOOR #5 WHICH |
| | ENCLOSES THE AHU #2 CLOSET IS A WOOD DOOR WHICH IS |
| | COMPLIANT IF THE RETURN IS DUCTED DIRECTLY TO THE AHU. |
| | OTHERWISE A NON-COMBUSTIBLE DOOR IS REQUIRED PER |
| | SECTIONS |
| | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND |
| | SECTION 602 FBC-14 MECHANICAL. |
| | |
| | 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR THE |
| | RTU AND CONDENSER INSTALLATIONS- SEE SECTION 301.15 |
| | FBC-14 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. |
| | |
| | 5) M-2: CORRECT NOTE #3 AT THE AHU MOUNTING DETAIL |
| | WHICH IS REFERENCING A RESIDIENTIAL CODE SECTION, AND |
| | SEE SECTION C403.2.7.3.3 WHICIH REQUIRES A MINIMUM 4" |
| | CLEARANCE SPACE AROUND THE AIR HANDLER. |
| | |
| | 6) ENERGYGAUGE COMPLIANCE SUBMITTAL: A) THE |
| | OWNER/AGENT'S SIGNATURE IS MISSING- PAGE 3. B) THE |
| | DESIGNER OR ENGINEER'S MANDATORY REQUIREMENTS CHECKLIST |
| | NOT COMPLETED- PAGE 8. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |