| 2017-06-28 15:31:24 | 2201 NORTH AUSTRALIAN AVENUE - CLUBHOUSE |
| | PERMIT #17060192 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET LS: |
| | |
| | PLAN SCALE IS INCORRECTLY INDICATED AS 1/4"=1'-0". |
| | |
| | NOTE #6 STATES, "AN NFPA 13 COMPLIANT SPRINKLER SYSTEM |
| | IS REQUIRED FOR THIS STRUCTURE"; HOWEVER, THE CLUBHOUSE |
| | SCOPE OF WORK STATES THIS IS A NON-SPRINKLERED |
| | BUILDING. |
| | |
| | PROVIDE A FURNITURE/EQUIPMENT PLAN JUSTIFYING THE USAGE |
| | OF THE 15 AND 50 SQ.FT. PER PERSON OCCUPANT LOAD |
| | FACTORS. |
| | |
| | THE TWO NORTH ARROW COMPASSES ON THE PLAN CONFLICT WITH |
| | EACHOTHER. |
| | |
| | HOW IS THE CLUBHOUSE FIRE AND LIFE SAFETY AFFECTED BY |
| | THE COVERED PATIO AND POOL AREA? NO INFORMATION |
| | SUBMITTED. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET A-11: SEVERAL WALLS INDICATE A FIRE RESISTANCE |
| | RATING; HOWEVER, ONLY DOOR #10 INDICATES IT HAS A FIRE |
| | RATING. |
| | |
| | GENERAL: NO CIVIL PLANS SUBMITTED. |
| | |
| | GENERAL: PER NFPA 241 SECTION 8.7.2.3, WHERE |
| | UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE |
| | PROVIDED, THEY SHALL BE INSTALLED, TESTED, APPROVED, |
| | AND IN SERVICE PRIOR TO VERTICAL CONSTRUCTION WORK. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |
| | |