| 2017-09-05 11:32:18 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | PREVIOUS COMMENT 1. ONLY THE GROUND FLOOR UNITS WILL BE |
| | REQUIRED TO COMPLY TO THE FHA AS A MIN CODE REQUIREMENT |
| | THE PLAN IS STATING THAT THE FIRST FLOOR WILL COMPLY |
| | WITH THE FLORIDA ACCESSIBILITY CODE AND FLOORS 2 AND 3 |
| | WILL COMPLY WITH FHA IS THIS CORRECT PLEASE CLARIFY. |
| | ALSO SEE BUILDING 1. COMMENT . |
| | |
| | PREVIOUS COMMENT 2. WHAT IS WORKFORCE HOUSING IS THIS |
| | PROJECT FEDERALLY FUNDED. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PREVIOUS COMMENT 13, SHT. P-1 THE SANITARY PLAN FOR 2ND |
| | AND 3RD FLOOR THE APARTMENTS ARE LABELED 101-104 PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PREVIOUS COMMENT 14. PROVIDE MANUFACTURE SPECIFICATIONS |
| | FOR SUB WATER METER AND BACK FLOW . PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. A6.3 DETAIL 3(A) THE END OF THE GRAB BAR |
| | BACKING SHALL BEGIN AT THE FRONT EDGE OF THE TUB AND |
| | EXTEND 24" TO BACK WALL . PER FHA DESIGN MANUAL PG. 6.9 |
| | |
| | 2.SHT. A6.3 SHOW GRAB BAR BACKING AT FOOT OF TUB. PER |
| | FHA DESIGN MANUAL PG.6.8 |
| | |
| | 3. SHT. A6.3 DETAIL 3(B) THE GRAB BAR BACKING ON BACK |
| | WALL OF TUB SHALL BEGIN 6" MAX FROM THE TOP OF THE TUB |
| | AND EXTEND A MIN OF 38" TO THE TOP. PER FHA DESIGN |
| | MANUAL PG. 6.9 |
| | |
| | 4. IT DOES NOT APPEAR THAT HALF OF THE AREA OF THE |
| | PARAPET AND WALLS ARE INCLUDED IN THE SQFT DRAIN BY |
| | ROOF DRAINS PLEASE CLARIFY. PER FBC PL 1106.5 PARAPET |
| | WALL SCUPPER LOCATION. |
| | PARAPET WALL ROOF DRAINAGE SCUPPER AND OVERFLOW SCUPPER |
| | LOCATION SHALL COMPLY WITH THE REQUIREMENTS OF SECTION |
| | 1503.4 OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 5. PLEASE PROVIDE A NOTE ON THE PLAN STATING THAT |
| | SEPARATE PERMITS ARE REQUIRED FOR ALL BACKFLOW |
| | PREVENTER'S. PER WPB AMEND TO FBC 107.2.1 AND UTILITIES |
| | DEPT |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |