Plan Review Notes
Plan Review Notes For Permit 17060191
Permit Number 17060191
Review Stop P
Sequence Number 2
Notes
Date Text
2017-09-05 11:32:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT 1. ONLY THE GROUND FLOOR UNITS WILL BE
 REQUIRED TO COMPLY TO THE FHA AS A MIN CODE REQUIREMENT
 THE PLAN IS STATING THAT THE FIRST FLOOR WILL COMPLY
 WITH THE FLORIDA ACCESSIBILITY CODE AND FLOORS 2 AND 3
 WILL COMPLY WITH FHA IS THIS CORRECT PLEASE CLARIFY.
 ALSO SEE BUILDING 1. COMMENT .
  
 PREVIOUS COMMENT 2. WHAT IS WORKFORCE HOUSING IS THIS
 PROJECT FEDERALLY FUNDED. PER WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENT 13, SHT. P-1 THE SANITARY PLAN FOR 2ND
 AND 3RD FLOOR THE APARTMENTS ARE LABELED 101-104 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENT 14. PROVIDE MANUFACTURE SPECIFICATIONS
 FOR SUB WATER METER AND BACK FLOW . PER WPB AMEND TO
 FBC 107.2.1
  
 NEW COMMENTS:
  
 1. SHT. A6.3 DETAIL 3(A) THE END OF THE GRAB BAR
 BACKING SHALL BEGIN AT THE FRONT EDGE OF THE TUB AND
 EXTEND 24" TO BACK WALL . PER FHA DESIGN MANUAL PG. 6.9
  
 2.SHT. A6.3 SHOW GRAB BAR BACKING AT FOOT OF TUB. PER
 FHA DESIGN MANUAL PG.6.8
  
 3. SHT. A6.3 DETAIL 3(B) THE GRAB BAR BACKING ON BACK
 WALL OF TUB SHALL BEGIN 6" MAX FROM THE TOP OF THE TUB
 AND EXTEND A MIN OF 38" TO THE TOP. PER FHA DESIGN
 MANUAL PG. 6.9
  
 4. IT DOES NOT APPEAR THAT HALF OF THE AREA OF THE
 PARAPET AND WALLS ARE INCLUDED IN THE SQFT DRAIN BY
 ROOF DRAINS PLEASE CLARIFY. PER FBC PL 1106.5 PARAPET
 WALL SCUPPER LOCATION.
 PARAPET WALL ROOF DRAINAGE SCUPPER AND OVERFLOW SCUPPER
 LOCATION SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 1503.4 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 5. PLEASE PROVIDE A NOTE ON THE PLAN STATING THAT
 SEPARATE PERMITS ARE REQUIRED FOR ALL BACKFLOW
 PREVENTER'S. PER WPB AMEND TO FBC 107.2.1 AND UTILITIES
 DEPT
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  