2017-08-18 08:15:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 17060191 3 STORY APARTMENT BUILDING
 17060189 6 STORY APARTMENT BUILDING
 17060192 CLUBHOUSE (BLDG F)
  
 COMMENTS FROM PREVIOUS LIST:
  
 1-2. OK
  
 3. SEE COMMENT FROM PREVIOUS LIST. 2ND REVIEW, PLANS
 HAVE BEEN REVISED TO STATE "THIS PLANS COMPLY WITH
 FLORIDA ACCESSIBILITY CODE(1ST LEVEL) & FAIR HOUSING
 ACT (ENTIRE BUILDING)". APPLICANT MAY EXCEED MINIMUM
 CODE BUT, IF PLAN STATES THAT INTENT IS TO COMPLY WITH
 A MORE STRINGENT REQUIREMENT, DESIGN MUST COMPLY.
  
 MINIMUM REQUIREMENT IS FAIR HOUSING COMPLIANCE ON THE
 GROUND FLOOR, NO ADA COMPLIANCE REQUIRED.
  
 SINCE THE PLAN STATES THAT THE INTENT IS FOR THE DESIGN
 TO COMPLY WITH ADA ON THE FIRST FLOOR, NOTE THAT THE
 FOLLOWING ITEMS DO NOT COMPLY WITH FLORIDA
 ACCESSIBILITY: BATHROOM DOOR LACKS 18" MANEUVERING
 CLEARANCE PULL SIDE FBC A TABLE 404.2.4; THE SLIDING
 GLASS DOOR TRACK DOES NOT COMPLY WITH ADA ACCESSIBLE
 ROUTE. OTHER ITEMS, SUCH AS REACH RANGES, NOT REVIEWED
 AS DESIGN INTENT IS NOT CLEAR.
  
 YOU MAY FIND THE FOLLOWING WEBSITE HELPFUL:
  
 HTTPS://PORTAL.HUD.GOV/HUDPORTAL/HUD?SRC=/PROGRAM_OFFIC
 ES/FAIR_HOUSING_EQUAL_OPP/DISABILITIES/ACCESSIBILITYR
  
 ADA IS GENERALLY APPLICABLE TO PLACES OF PUBLIC
 ACCOMODATION, NOT LONG TERM HOUSING. IT IS RECOMMENDED
 TO REVISE PLAN TO NOTE FAIR HOUSING COMPLIANCE, FIRST
 FLOOR, AND REMOVE ADA REFERENCES. EVEN FAIR HOUSING
 REFERENCE FOR FLOORS OTHER THAN THE GROUND FLOOR IS
 CONFUSING AS THERE IS NO ELEVATOR. IT IS RECOMMENDED TO
 REMOVE THE REFERENCE REGARDING FAIR HOUSING COMPLIANCE
 ON FLOORS ABOVE THE GROUND FLOOR.
  
 4. OK
  
 5. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION
 REPORT (S1.0 ARDAMAN & ASSOC 2/10/17). THIS IS AREA IS
 KNOWN TO HAVE THE POTENTIAL OF POOR SOILS.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THE SOILS ARE
 WITH THE FULL SET. EACH PERMIT REQUIRES DOCUMENTS TO
 SHOW COMPLIANCE FOR THE PERMIT; EACH PERMIT IS
 TRAVELLING SEPARATELY. UNTIL ONE PERMIT IS ISSUED, THE
 SOILS REPORT WHICH WAS SUBMITTED WITH ONE OF THE TWO
 OTHER PERMITS IS NOT A PART OF THE PUBLIC RECORD.
 PLEASE PROVIDE THREE COPIES OF THE SOILS REPORT WITH
 EACH PERMIT APPLICATION. ONE PERMIT APPLICATION SHOULD
 INCLUDE ORIGINAL SIGNED AND SEALED SOILS REPORTS; THE
 SOILS REPORTS SUBMITTED WITH THE OTHER TWO ASSOCIATED
 PERMITS MAY BE PHOTOCOPIES.
  
 I ATTEMPTED TO LOCATE THE SOILS REPORT WHICH WAS
 SUBMITTED WITH ANOTHER PERMIT APPLICATION. IT APPEARS
 THAT THE OTHER APPLICATIONS HAVE BEEN CHECKED OUT FOR
 REVIEW BY ANOTHER REVIEWER, SO REVIEW OF THE FOUNDATION
 AND THE SOILS REPORT IS NOT POSSIBLE AT THIS TIME.
 STRUCTURAL REVIEW INCLUDES VERIFICATION OF THE SOILS
 ENGINEER'S RECOMMENDATIONS.
  
 6. OK
  
 7. CLARIFY ZONE 3 DIMENSION AND DIMENSION OF OVERHANG
 OF ROOF OVER THE STAIR, FBC 107 (NORTH AND SOUTH
 OVERHANGS).
  
 2ND REVIEW, RESPONSE LETTER REFERS TO SHEET A-1.5.
 PLEASE SEE A-1.5 AND A-3.3. THE STAIRS HAVE A ROOF WITH
 NO PARAPET; OVERHANG PRESSURES APPEAR APPLICABLE FOR A
 PORTION OF THE STAIR ROOF, BUT IT APPEARS THAT A
 PORTION OF ZONE 3 ROOF IS NOT OVERHANG. IF ANY PORTION
 OF ZONE 3 IS NOT OVERHANG, THEN ZONE 3 ROOF DESIGN
 PRESSURE SPECIFIED ON SHEET S1.0 (-77.6PSF, SAME AS
 ZONE 2 PRESSURES) APPEARS TOO LOW FOR THE STAIR ROOF
 (OK FOR APARTMENT ROOF). PLEASE REVISE PLAN TO CLARIFY.
 IF YOU WISH TO DISCUSS, OR DISAGREE, PLEASE CONTACT ME.
  
 8-10. OK
  
 11. A 2 HOUR PARTITION IS SHOWN BETWEEN UNITS, BUT FIRE
 RESISTANCE OF THE WALL BETWEEN THE UNITS ON THE
 BALCONIES AND PORCHES IS NOT CLEAR, REVISE PLAN TO
 CLARIFY, FBC 107. PLEASE ALSO REVISE LANGUAGE FROM
 "SEPARATION" TO "PARTITION" (FBC B 708).
  
 RESPONSE STATES THAT SHEETS WERE REVISED, BUT PLAN DOES
 NOT SHOW A RATED WALL BETWEEN THE UNIT BALCONIES. IF
 DOR DOES NOT AGREE WITH COMMENT, PLEASE CONTACT ME TO
 DISCUSS PRIOR TO RESUBMITTAL. IF DOR AGREES, PLEASE
 REVISE THE EXTERIOR WALL BETWEEN THE UNITS ON THE
 BALCONIES TO INDICATE MINIMUM 1 HOUR; THIS CAN BE A
 NOTE, NO DETAIL REQUIRED. THE UL WALL DETAIL IS NOT
 APPLICABLE TO THE BALCONY LOCATION AS THE UL WALL
 DETAIL HAS AN INTERIOR AND EXTERIOR SIDE. BALCONY WALL
 HAS TWO EXTERIOR SIDES.
  
 12. FBC B 1503.4, FBC B 1503.4.1, FBC P 1106.4, SHEET
 A-1.5, IT DOES NOT APPEAR THAT 50% OF THE STAIR WALL
 WAS INCLUDED IN THE CALCULATIONS; REVISE PLAN TO
 INCLUDE OR CLARIFY. ALSO PROVIDE PARAPET CALCS; IT IS
 NOT CLEAR IF THE HIGHER WALL OVER THE BALCONY AREAS WAS
 INCLUDED IN PARAPET CALCS.
  
 13. REGARDING THE ENERGY CALCS: PLEASE CORRECT COUNTY
 (STATES BROWARD) IF ENERGY CALCS ARE REVISED DUE TO
 ANOTHER COMMENTS; OTHERWISE ENERGY CALCS APPEAR
 COMPLIANT.
  
 14. OK
  
 15. FBC B 1207.2, 1207.3, PROVIDE TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT (STC/IIC). REVISE PLAN TO INCLUDE
 REQUIREMENT FOR ACOUSTIC INSULATION. NOTE THAT SPEC
 SHEETS ARE NOT ACCEPTABLE; ACTUAL TEST REPORTS ARE
 REVIEWED. IT IS LIKELY THAT THE MANUFACTURER WILL BE
 REQUIRED TO DO A COMPARATIVE ANALYSIS AS IT IS UNLIKELY
 THAT THE UNDERLAYMENT WAS TESTED WITH HOLLOW CORE (MOST
 TESTS ARE DONE WITH A CONCRETE SLAB).
  
 2ND REVIEW, PLAN HAS BEEN REVISED IN AN ACCEPTABLE
 MANNER. PLEASE ALSO REVISE COVER PAGE "TO BE SUBMITTED
 AT A LATER TIME OR UNDER SEPARATE PERMITS" - PLEASE ADD
 "FLOORING UNDERLAYMENT STC/IIC TEST REPORTS" TO THIS
 LIST. SEE ALSO ADVISORY UNDER ITEM #16.
  
 HOWEVER, RESPONSE LETTER STILL REFERS TO "CSM". THIS IS
 A BRAND, NO TEST REPORTS HAVE BEEN PROVIDED. IT IS NOT
 CLEAR IF THIS PRODUCT CAN BE USED.
  
 16. FBC 720.2, PROVIDE A COPY OF THE FLAME SPREAD TEST
 FOR THE PROPOSED FLOORING UNDERLAYMENT.
  
 2ND REVIEW, RESPONSE IS THAT CSM PRODUCT WILL BE
 PROVIDED AT A LATER DATE. THIS IS ACCEPTABLE; PLEASE
 REVISE THE FRONT PAGE TO ADD "FLOORING UNDERLAYMENT
 FLAME SPREAD REPORT". HOWEVER:
  
 HOWEVER, RESPONSE LETTER STILL REFERS TO "CSM". THIS IS
 A BRAND, NO TEST REPORTS HAVE BEEN PROVIDED. IT IS NOT
 CLEAR IF THIS PRODUCT CAN BE USED.
  
 ***PLEASE BE ADVISED THAT, TO MY KNOWLEDGE, ONLY ONE
 PRODUCT HAS THE THREE TEST REPORTS REQUIRED (STC, IIC,
 FLAME SPREAD) - MOST PRODUCTS DO NOT HAVE A FLAME
 SPREAD TEST WITHOUT TILE ON THE FLAME SIDE IN THE
 STEINER TUNNEL - THIS IS NOT ACCEPTABLE FOR A LVT
 INSTALLATION. MANY PRODUCTS DO NOT HAVE AN STC/IIC
 WITHOUT DROPPED GYPSUM CEILING, ALSO NOT ACCEPTABLE***
  
 I AM CONCERNED AS THIS APPLICATION IS "TBD" (NO
 CONTRACTOR) AND ALSO IS PRIVATE PROVIDER. A C.O. WILL
 NOT BE ISSUED UNLESS THE THREE TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT HAVE BEEN PROVIDED AND THE JOB
 INSPECTOR HAS CONFIRMED THAT THE CORRECT UNDERLAYMENT
 (SUBMITTED AND REVIEWED) HAS BEEN INSTALLED.
  
 HOW DOES APPLICANT (ARCHITECT, DEVELOPER, OR OWNER)
 PROPOSE TO CONVEY THIS INFORMATION TO THE FUTURE
 CONTRACTOR? THIS IS A RESTRICTIVE REQUIREMENT WHICH IS
 NOT ENFORCED IN ALL JURISDICTIONS, SO CONTRACTOR MAY BE
 UNFAMILIAR WITH THE REQUIREMENT. WE HAVE FOUND THAT
 MOST PRODUCTS DO NOT HAVE THE THREE TEST REPORTS WHICH
 DEMONSTRATE CODE COMPLIANCE.
  
 IS IT POSSIBLE TO HAVE APPLICANT'S PRODUCT OF CHOICE'S
 TECHNICAL REPRESENTATIVE CONTACT ME DIRECTLY SO WE CAN
 WORK THROUGH THIS TO AVOID POTENTIAL FUTURE ISSUES?
  
 17. OK
  
 18. THIS PERMIT WILL BE ISSUED WITH PROVISO, A SEPARATE
 ROOF PERMIT IS REQUIRED. A ROOF PRODUCT APPROVAL WAS
 SUBMITTED, FIBERTITE SINGLE PLY ROOF SYSTEMS OVER
 LIGHTWEIGHT CONCRETE DECKS (NOA 15-1026.04).
  
 AT TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED
 ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE
 REQUIRED AT THAT TIME.
  
 19. FS 553.80, A 4X FEE WILL BE CHARGED (AS REQUIRED BY
 LAW) IF COMMENTS ARE NOT ADDRESSED A THIRD TIME (#7,
 #11).
  
  
  
 ************************************
 INTERNAL USE ONLY
 17060191 BUILDING DATA FOR C.O./REPORTING
  
 USC-404 105 - NEW: RES FIVE OR MORE UNITS
 SQUARE FEET - 11429
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 12
 FLOORS: 3
 BEDROOMS: 24
 ROOMS: 48
 SQ FT LIVABLE: 11429
 SQ FT FOOTPRINT: 3452
 SQ FT ROOF: 3452
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 58
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 12
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  