| 2017-07-06 11:39:59 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. ONLY THE GROUND FLOOR UNITS WILL BE REQUIRED TO |
| | COMPLY TO THE FHA |
| | |
| | 2. WHAT IS WORKFORCE HOUSING IS THIS PROJECT FEDERALLY |
| | FUNDED. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE CLARIFY ON THE PLAN WHICH DESIGN |
| | SPECIFICATION A OR B THAT YOU WILL BE USING ON EACH |
| | UNIT. PER FHA |
| | |
| | 4. PLEASE INDICATE ON THE PLAN WHICH DOCUMENT THE FHA |
| | DESIGN MANUAL OR THE FHA GUIDELINES FOUND IN FBC ACC, |
| | YOU WILL BE USING TO DESIGN THE ELEMENTS TO COMPLY WITH |
| | THE FHA . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHOW THE CLEAR FLOOR SPACE FOR THE FIXTURES IN THE |
| | BATHROOM AND KITCHEN. PER FHA |
| | |
| | 6. PROVIDE MOUNTING HEIGHT DIMENSIONS FOR THE GRAB BAR |
| | BACK AT THE TOILET AND TUB. PER FHA |
| | |
| | 7. PROVIDE RISER DIAGRAM FOR ROOF DRAINS PER WPB AMEND |
| | TO FBC 107.3.5.1.3(13) |
| | |
| | 8. PLEASE SHOW ON THE PLANS THE SQUARE FOOTAGE BEING |
| | DRAINED BY EACH ROOF DRAIN . PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 9. PROVIDE COMPLIANCE WITH FBC PL 1108.1 SECONDARY |
| | (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. |
| | WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY |
| | OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED |
| | WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE |
| | ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF |
| | THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. |
| | |
| | 10. TERMINATION OF THE PAN DRAINS SHALL COMPLY WITH FBC |
| | PL 504.7.2 PAN DRAIN TERMINATION. |
| | THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER |
| | A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR |
| | DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND |
| | TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE |
| | THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND |
| | SURFACE. |
| | |
| | 11. SHOW ALL CLEAN OUTS ON RISER PER FBC PL 708.3.4 |
| | BASE OF STACK. |
| | A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE |
| | OR SOIL STACK. |
| | |
| | 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| | THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT |
| | SHALL BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL AND |
| | SHALL BE BROUGHT UP TO THE FINISHED GROUND LEVEL OR TO |
| | THE BASEMENT FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT |
| | IS ALLOWED TO BE USED AT THIS LOCATION TO SERVE AS A |
| | REQUIRED CLEANOUT FOR BOTH THE BUILDING DRAIN AND |
| | BUILDING SEWER. THE CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER SHALL NOT BE REQUIRED |
| | IF THE CLEANOUT ON A 3-INCH (76 MM) OR LARGER DIAMETER |
| | SOIL STACK IS LOCATED WITHIN A DEVELOPED LENGTH OF 10 |
| | FEET (3048 MM) OF THE BUILDING DRAIN AND BUILDING SEWER |
| | CONNECTION. THE MINIMUM SIZE OF THE CLEANOUT AT THE |
| | JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER SHALL |
| | COMPLY WITH SECTION 708.7. |
| | |
| | 12. PROVIDE RISER FOR WATER HEATER PAN DRAIN. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 13, SHT. P-1 THE SANITARY PLAN FOR 2ND AND 3RD FLOOR |
| | THE APARTMENTS ARE LABELED 101-104 PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 14. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB WATER |
| | METER AND BACK FLOW . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |