| 2017-06-29 16:59:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 17060191 3 STORY APARTMENT BUILDING |
| | 17060189 6 STORY APARTMENT BUILDING |
| | 17060192 CLUBHOUSE (BLDG F) |
| | |
| | 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE |
| | CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT |
| | ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH |
| | PAGE. |
| | |
| | 2. FS471.0195, THE DBPR RECORD FOR THE FOLLOWING |
| | ENGINEER(S) DO NOT REFLECT THAT THE ADVANCED FLORIDA |
| | BUILDING CODE COURSE HAS BEEN COMPLETED. EMAIL THE |
| | CERTIFICATE TO FBPE AND REQUEST THAT THE DBPR RECORD BE |
| | UPDATED. NOTE THAT IT IS POSSIBLE THAT THE COURSE WAS |
| | COMPLETED AND THE WEBSITE IS NOT CURRENT. |
| | |
| | SANTIAGO ARANEGUI, PE |
| | JOE SPASOVSKI, PE |
| | |
| | PERMIT ISSUANCE WILL NOT BE DELAYED DUE TO THIS |
| | COMMENT. HOWEVER, FLORIDA STATUTE REQUIRES THAT: |
| | LOCAL JURISDICTIONS SHALL BE RESPONSIBLE FOR NOTIFYING |
| | THE BOARD WHEN DESIGN DOCUMENTS ARE SUBMITTED FOR |
| | BUILDING CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN |
| | COMPLIANCE WITH THIS SECTION. |
| | |
| | 3. SHEET A1.1 (AND OTHER PAGES), FBC A FAIR HOUSING, |
| | REVISE PLAN TO SHOW COMPLIANCE WITH REQUIREMENTS. THERE |
| | IS A GENERAL NOTE STATING "THIS PLANS COMPLY WITH THE |
| | FLORIDA ACCESSIBILITY CODE & FAIR HOUSING ACT" (SIC). |
| | |
| | IT IS NOT CLEAR WHAT THAT MEANS. THE FBC IS A MINIMUM |
| | CODE, DESIGNER/OWNER/APPLICANT CAN ELECT TO EXCEED THE |
| | MINIMUM REQUIREMENTS OF THE FLORIDA BUILDING CODE. WHEN |
| | DESIGNER DECLARES THAT HE/SHE IS EXCEEDING CODE VIA THE |
| | PERMIT DOCUMENTS, THE DESIGN CRITERIA DECLARED BY THE |
| | DESIGNER IS ENFORCED. |
| | |
| | DOES APPLICANT WISH FOR FLORIDA ACCESSIBILITY CODE TO |
| | BE APPLIED TO THIS PERMIT? NOTE THAT VERTICAL |
| | ACCESSIBILITY WAS NOT PROVIDED, PLAN DOES NOT COMPLY |
| | WITH MANEUVERING CLEARANCE REQUIREMENTS. THESE ITEMS |
| | ARE NOT REQUIRED FOR FAIR HOUSING, BUT ARE REQUIRED FOR |
| | COMPLIANCE WITH FBC ACCESSIBLIITY. |
| | |
| | EITHER REVISE THE STATEMENT, OR REVISE THE PLAN TO SHOW |
| | COMPLIANCE WITH ACCESSIBILITY. |
| | |
| | 4. REVISE THE PLAN TO SHOW FAIR HOUSING COMPLIANCE. FOR |
| | INSTANCE, BATHROOMS ARE NOT IDENTIFIED AS SPECIFICATION |
| | A OR SPECIFICATION B, CLEAR FLOOR SPACE AND MANEUVERING |
| | CLEARANCE NOT MARKED, GRAB BAR BACKING DETAIL NOT |
| | PROVIDED. |
| | |
| | 5. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION |
| | REPORT. THIS IS AREA IS KNOWN TO HAVE THE POTENTIAL OF |
| | POOR SOILS. |
| | |
| | 6. S1.0, DESIGN PRESSURES DO NOT STATE ULTIMATE OR ASD |
| | FOR COMPONENT AND CLADDING PRESSURES, FBC 107. WIND |
| | DESIGN CRITERIA SHOULD INCLUDE BOTH (SEE FBC B |
| | 1603.1.4), ONLY ASD WIND SPEED WAS INCLUDED, C&C |
| | PRESSURES APPEAR TO BE ASD BUT NOT STATED AS SUCH, |
| | PLEASE CLARIFY. |
| | |
| | 7. CLARIFY ZONE 3 DIMENSION AND DIMENSION OF OVERHANG |
| | OF ROOF OVER THE STAIR, FBC 107 (NORTH AND SOUTH |
| | OVERHANGS). |
| | |
| | 8. S1.0, ROOF LIVE LOAD IS 20PSF; FBC B TABLE 1607.1 |
| | REQUIRES 300 CONCENTRATED FOR "ALL ROOF SURFACES |
| | SUBJECT TO MAINTENANCE WORKERS". RTU EQUIPMENT SHOWN. |
| | EITHER REVISE DESIGN CRITERIA FOR THIS ROOF SECTION OR |
| | PROVIDE RATIONALE FOR 20PSF LIVE LOAD. |
| | |
| | 9. IT APPEARS THAT NOT ALL LAP SPLICES WERE SPECIFIED |
| | ON THE PLAN FOR THE FOUNDATION; REVISE PLAN OR ADVISE |
| | WHERE THIS CAN BE LOCATED, FBC 107, FBC B CHAPTER 19. |
| | |
| | 10. FBC B 420.3, PROVIDE A DETAIL SHOWING COMPLIANCE |
| | WITH THE 1 HOUR SEPARATION REQUIREMENT FOR THE |
| | FLOOR/CEILING ASSEMBLIES BETWEEN UNITS. REVISE THE PLAN |
| | TO SHOW THE 1 HOUR (MINIMUM) FLOOR/CEILING ASSEMBLY. |
| | |
| | 11. A 2 HOUR PARTITION IS SHOWN BETWEEN UNITS, BUT FIRE |
| | RESISTANCE OF THE WALL BETWEEN THE UNITS ON THE |
| | BALCONIES AND PORCHES IS NOT CLEAR, REVISE PLAN TO |
| | CLARIFY, FBC 107. PLEASE ALSO REVISE LANGUAGE FROM |
| | "SEPARATION" TO "PARTITION" (FBC B 708). |
| | |
| | 12. DETAIL 1-A1.6 REFERS TO PLUMBING DRAWINGS FOR DRAIN |
| | SIZE, UNABLE TO LOCATE. REVISE PLAN TO INCLUDE ROOF |
| | DRAIN INFORMATION (SIZES, CALCULATIONS), FBC B 1503.4, |
| | AND OVERFLOW SCUPPER SIZING INFORMATION FBC B 1503.4.1. |
| | |
| | 13. ENERGY CALCS REQUIRED, FBC EC R103. |
| | |
| | 14. A1.1 NOTE 3 STATES THAT NFPA 13 SPRINKLERS WILL BE |
| | INSTALLED, BUT FS2 PROPOSES NFPA13R, PLEASE CORRELATE. |
| | |
| | 15. FBC B 1207.2, 1207.3, PROVIDE TEST REPORTS FOR THE |
| | FLOORING UNDERLAYMENT (STC/IIC). REVISE PLAN TO INCLUDE |
| | REQUIREMENT FOR ACOUSTIC INSULATION. NOTE THAT SPEC |
| | SHEETS ARE NOT ACCEPTABLE; ACTUAL TEST REPORTS ARE |
| | REVIEWED. IT IS LIKELY THAT THE MANUFACTURER WILL BE |
| | REQUIRED TO DO A COMPARATIVE ANALYSIS AS IT IS UNLIKELY |
| | THAT THE UNDERLAYMENT WAS TESTED WITH HOLLOW CORE (MOST |
| | TESTS ARE DONE WITH A CONCRETE SLAB). |
| | |
| | CSM CRACK SUPPRESSION & SOUND CONTROL SPEC SHEET WAS |
| | PROVIDED. PLEASE SEND TEST REPORTS VIA EMAIL FOR |
| | PRELIMINARY REVIEW. WHEN REVISING PLAN TO INCLUDE |
| | UNDERLAYMENT REQUIREMENT, IT IS ADVISED THAT YOU DO NOT |
| | SPEC A PRODUCT. |
| | |
| | 16. FBC 720.2, PROVIDE A COPY OF THE FLAME SPREAD TEST |
| | FOR THE PROPOSED FLOORING UNDERLAYMENT. |
| | |
| | 17. AS THIS IS NEW CONSTRUCTION, APPLY FOR AN |
| | ENGINEERING PERMIT; 561-494-1040. ENGINEERING |
| | DEPARTMENT APPROVAL IS REQUIRED PRIOR TO PERMIT |
| | ISSUANCE. CONTACT THEM DIRECTLY REGARDING REQUIREMENTS. |
| | IF YOU HAVE ALREADY APPLIED, PROVIDE THE APPLICATION |
| | NUMBER. I WAS UNABLE TO LOCATE AN ENGINEERING |
| | APPLICATION FOR THIS PARCEL ID. |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 18. A SEPARATE ROOF PERMIT IS REQUIRED. A ROOF PRODUCT |
| | APPROVAL WAS SUBMITTED, FIBERTITE SINGLE PLY ROOF |
| | SYSTEMS OVER LIGHTWEIGHT CONCRETE DECKS (NOA |
| | 15-1026.04). |
| | |
| | FBC 1609, AT THIS TIME, APPLICANT MAY INDICATE WHICH |
| | APPROVED ASSEMBLY IS PROPOSED. IF THIS IS DONE NOW, THE |
| | ROOF SUB PERMIT WILL BE ISSUED WITHOUT ANY OTHER |
| | INFORMATION REQUIRED. |
| | |
| | IF APPLICANT DOES NOT PROVIDE THIS INFORMATION AT THIS |
| | TIME, THIS PERMIT WILL BE ISSUED WITH PROVISO THAT, AT |
| | TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED |
| | ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE |
| | REQUIRED AT THAT TIME. |
| | |
| | ************************************ |
| | INTERNAL USE ONLY |
| | 17060191 BUILDING DATA FOR C.O./REPORTING |
| | |
| | USC-404 105 - NEW: RES FIVE OR MORE UNITS |
| | SQUARE FEET - 11429 |
| | |
| | CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B |
| | UNITS: 12 |
| | FLOORS: 3 |
| | BEDROOMS: 24 |
| | ROOMS: 48 |
| | SQ FT LIVABLE: 11429 |
| | SQ FT FOOTPRINT: 3452 |
| | SQ FT ROOF: 3452 |
| | |
| | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| | KNOWN): |
| | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| | XX.XX |
| | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| | XX.XX |
| | OCC LOAD: 58 |
| | PROP USE: APARTMENT |
| | SPRINKLER SYS? Y |
| | SPRK REQ'D? Y |
| | BATHRMS: |
| | |
| | BLDG CODE: FL 2014 |
| | OCC CLASS: 5TH ED R-2 |
| | |