Plan Review Notes
Plan Review Notes For Permit 17060191
Permit Number 17060191
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-29 16:59:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 17060191 3 STORY APARTMENT BUILDING
 17060189 6 STORY APARTMENT BUILDING
 17060192 CLUBHOUSE (BLDG F)
  
 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE
 CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT
 ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH
 PAGE.
  
 2. FS471.0195, THE DBPR RECORD FOR THE FOLLOWING
 ENGINEER(S) DO NOT REFLECT THAT THE ADVANCED FLORIDA
 BUILDING CODE COURSE HAS BEEN COMPLETED. EMAIL THE
 CERTIFICATE TO FBPE AND REQUEST THAT THE DBPR RECORD BE
 UPDATED. NOTE THAT IT IS POSSIBLE THAT THE COURSE WAS
 COMPLETED AND THE WEBSITE IS NOT CURRENT.
  
 SANTIAGO ARANEGUI, PE
 JOE SPASOVSKI, PE
  
 PERMIT ISSUANCE WILL NOT BE DELAYED DUE TO THIS
 COMMENT. HOWEVER, FLORIDA STATUTE REQUIRES THAT:
 LOCAL JURISDICTIONS SHALL BE RESPONSIBLE FOR NOTIFYING
 THE BOARD WHEN DESIGN DOCUMENTS ARE SUBMITTED FOR
 BUILDING CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN
 COMPLIANCE WITH THIS SECTION.
  
 3. SHEET A1.1 (AND OTHER PAGES), FBC A FAIR HOUSING,
 REVISE PLAN TO SHOW COMPLIANCE WITH REQUIREMENTS. THERE
 IS A GENERAL NOTE STATING "THIS PLANS COMPLY WITH THE
 FLORIDA ACCESSIBILITY CODE & FAIR HOUSING ACT" (SIC).
  
 IT IS NOT CLEAR WHAT THAT MEANS. THE FBC IS A MINIMUM
 CODE, DESIGNER/OWNER/APPLICANT CAN ELECT TO EXCEED THE
 MINIMUM REQUIREMENTS OF THE FLORIDA BUILDING CODE. WHEN
 DESIGNER DECLARES THAT HE/SHE IS EXCEEDING CODE VIA THE
 PERMIT DOCUMENTS, THE DESIGN CRITERIA DECLARED BY THE
 DESIGNER IS ENFORCED.
  
 DOES APPLICANT WISH FOR FLORIDA ACCESSIBILITY CODE TO
 BE APPLIED TO THIS PERMIT? NOTE THAT VERTICAL
 ACCESSIBILITY WAS NOT PROVIDED, PLAN DOES NOT COMPLY
 WITH MANEUVERING CLEARANCE REQUIREMENTS. THESE ITEMS
 ARE NOT REQUIRED FOR FAIR HOUSING, BUT ARE REQUIRED FOR
 COMPLIANCE WITH FBC ACCESSIBLIITY.
  
 EITHER REVISE THE STATEMENT, OR REVISE THE PLAN TO SHOW
 COMPLIANCE WITH ACCESSIBILITY.
  
 4. REVISE THE PLAN TO SHOW FAIR HOUSING COMPLIANCE. FOR
 INSTANCE, BATHROOMS ARE NOT IDENTIFIED AS SPECIFICATION
 A OR SPECIFICATION B, CLEAR FLOOR SPACE AND MANEUVERING
 CLEARANCE NOT MARKED, GRAB BAR BACKING DETAIL NOT
 PROVIDED.
  
 5. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION
 REPORT. THIS IS AREA IS KNOWN TO HAVE THE POTENTIAL OF
 POOR SOILS.
  
 6. S1.0, DESIGN PRESSURES DO NOT STATE ULTIMATE OR ASD
 FOR COMPONENT AND CLADDING PRESSURES, FBC 107. WIND
 DESIGN CRITERIA SHOULD INCLUDE BOTH (SEE FBC B
 1603.1.4), ONLY ASD WIND SPEED WAS INCLUDED, C&C
 PRESSURES APPEAR TO BE ASD BUT NOT STATED AS SUCH,
 PLEASE CLARIFY.
  
 7. CLARIFY ZONE 3 DIMENSION AND DIMENSION OF OVERHANG
 OF ROOF OVER THE STAIR, FBC 107 (NORTH AND SOUTH
 OVERHANGS).
  
 8. S1.0, ROOF LIVE LOAD IS 20PSF; FBC B TABLE 1607.1
 REQUIRES 300 CONCENTRATED FOR "ALL ROOF SURFACES
 SUBJECT TO MAINTENANCE WORKERS". RTU EQUIPMENT SHOWN.
 EITHER REVISE DESIGN CRITERIA FOR THIS ROOF SECTION OR
 PROVIDE RATIONALE FOR 20PSF LIVE LOAD.
  
 9. IT APPEARS THAT NOT ALL LAP SPLICES WERE SPECIFIED
 ON THE PLAN FOR THE FOUNDATION; REVISE PLAN OR ADVISE
 WHERE THIS CAN BE LOCATED, FBC 107, FBC B CHAPTER 19.
  
 10. FBC B 420.3, PROVIDE A DETAIL SHOWING COMPLIANCE
 WITH THE 1 HOUR SEPARATION REQUIREMENT FOR THE
 FLOOR/CEILING ASSEMBLIES BETWEEN UNITS. REVISE THE PLAN
 TO SHOW THE 1 HOUR (MINIMUM) FLOOR/CEILING ASSEMBLY.
  
 11. A 2 HOUR PARTITION IS SHOWN BETWEEN UNITS, BUT FIRE
 RESISTANCE OF THE WALL BETWEEN THE UNITS ON THE
 BALCONIES AND PORCHES IS NOT CLEAR, REVISE PLAN TO
 CLARIFY, FBC 107. PLEASE ALSO REVISE LANGUAGE FROM
 "SEPARATION" TO "PARTITION" (FBC B 708).
  
 12. DETAIL 1-A1.6 REFERS TO PLUMBING DRAWINGS FOR DRAIN
 SIZE, UNABLE TO LOCATE. REVISE PLAN TO INCLUDE ROOF
 DRAIN INFORMATION (SIZES, CALCULATIONS), FBC B 1503.4,
 AND OVERFLOW SCUPPER SIZING INFORMATION FBC B 1503.4.1.
  
 13. ENERGY CALCS REQUIRED, FBC EC R103.
  
 14. A1.1 NOTE 3 STATES THAT NFPA 13 SPRINKLERS WILL BE
 INSTALLED, BUT FS2 PROPOSES NFPA13R, PLEASE CORRELATE.
  
 15. FBC B 1207.2, 1207.3, PROVIDE TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT (STC/IIC). REVISE PLAN TO INCLUDE
 REQUIREMENT FOR ACOUSTIC INSULATION. NOTE THAT SPEC
 SHEETS ARE NOT ACCEPTABLE; ACTUAL TEST REPORTS ARE
 REVIEWED. IT IS LIKELY THAT THE MANUFACTURER WILL BE
 REQUIRED TO DO A COMPARATIVE ANALYSIS AS IT IS UNLIKELY
 THAT THE UNDERLAYMENT WAS TESTED WITH HOLLOW CORE (MOST
 TESTS ARE DONE WITH A CONCRETE SLAB).
  
 CSM CRACK SUPPRESSION & SOUND CONTROL SPEC SHEET WAS
 PROVIDED. PLEASE SEND TEST REPORTS VIA EMAIL FOR
 PRELIMINARY REVIEW. WHEN REVISING PLAN TO INCLUDE
 UNDERLAYMENT REQUIREMENT, IT IS ADVISED THAT YOU DO NOT
 SPEC A PRODUCT.
  
 16. FBC 720.2, PROVIDE A COPY OF THE FLAME SPREAD TEST
 FOR THE PROPOSED FLOORING UNDERLAYMENT.
  
 17. AS THIS IS NEW CONSTRUCTION, APPLY FOR AN
 ENGINEERING PERMIT; 561-494-1040. ENGINEERING
 DEPARTMENT APPROVAL IS REQUIRED PRIOR TO PERMIT
 ISSUANCE. CONTACT THEM DIRECTLY REGARDING REQUIREMENTS.
 IF YOU HAVE ALREADY APPLIED, PROVIDE THE APPLICATION
 NUMBER. I WAS UNABLE TO LOCATE AN ENGINEERING
 APPLICATION FOR THIS PARCEL ID.
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 18. A SEPARATE ROOF PERMIT IS REQUIRED. A ROOF PRODUCT
 APPROVAL WAS SUBMITTED, FIBERTITE SINGLE PLY ROOF
 SYSTEMS OVER LIGHTWEIGHT CONCRETE DECKS (NOA
 15-1026.04).
  
 FBC 1609, AT THIS TIME, APPLICANT MAY INDICATE WHICH
 APPROVED ASSEMBLY IS PROPOSED. IF THIS IS DONE NOW, THE
 ROOF SUB PERMIT WILL BE ISSUED WITHOUT ANY OTHER
 INFORMATION REQUIRED.
  
 IF APPLICANT DOES NOT PROVIDE THIS INFORMATION AT THIS
 TIME, THIS PERMIT WILL BE ISSUED WITH PROVISO THAT, AT
 TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED
 ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE
 REQUIRED AT THAT TIME.
  
 ************************************
 INTERNAL USE ONLY
 17060191 BUILDING DATA FOR C.O./REPORTING
  
 USC-404 105 - NEW: RES FIVE OR MORE UNITS
 SQUARE FEET - 11429
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 12
 FLOORS: 3
 BEDROOMS: 24
 ROOMS: 48
 SQ FT LIVABLE: 11429
 SQ FT FOOTPRINT: 3452
 SQ FT ROOF: 3452
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 58
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  